6. TECHNICAL SPECIFICATIONS
6.1. CHARACTERISTICS
Accuracy is calculated as [% rdg + (number of dgt) x resolution]. It is referred to the
following reference conditions: 18°C ÷ 28°C (65°F ÷ 83°F) with RH < 75%
DC Voltage (Autorange)
Range Resolution Accuracy Input impedance
Overload
protection
600.0mV 0.01mV
±(1.0%rdg + 3dgt) 10M
1000VDC/ACrms
6.000V 0.001V
60.00V 0.01V
600.0V 0.1V
1000V 1V
The meter emits a continuous sound with VDC >1000V
AC Voltage TRMS (Autorange) – (instrument HT9014)
Range Resolution Accuracy
Input
impedance
Bandwidh
Overload
protection
6.000V 0.001V
±(1.0%rdg+10dgt)
(50 ÷ 60Hz)
±(3.5%rdg+5dgt)
(61 ÷ 400Hz)
10M
50-400Hz 1000VDC/ACrms
60.00V 0.01V
600.0V 0.1V
1000V 1V
Integrated sensor for AC voltage detection: LED turn on for phase-earth voltage > 100V, 50/60Hz
The meter emits a continuous sound on 1000V range for VAC>750V
AC Voltage TRMS (Autorange) – (instrument HT9015)
Range Resolution Accuracy
Input
impedance
Bandwidh
Overload
protection
6.000V 0.001V
±(1.0%rdg+10dgt)
(50 ÷ 60Hz)
±(3.5%rdg+5dgt)
(61 ÷ 400Hz)
10M
50-400Hz 1000VDC/ACrms
60.00V 0.01V
±(1.0%rdg.+4dgt)
(50 ÷ 60Hz)
±(3.5%rdg+5dgt)
(61 ÷ 400Hz)
600.0V 0.1V
1000V 1V
Integrated sensor for AC voltage detection: LED turn on for phase-earth voltage > 100V, 50/60Hz
The meter emits a continuous sound on 1000V range for VAC>750V
Resistance and Continuity test (Autorange)
Range Resolution Accuracy Buzzer Overload protection
600.0 0.1
±(1.0%rdg+5dgt)
60
600VDC/ACrms
6.000k 0.001k
60.00k 0.01k
600.0k 0.1k
6.000M 0.001M
60.00M 0.01M ±(2.0%rdg.+10dgt)
Test current of continuity test: < 0.35mA
DC Current (only HT9015)
Range Resolution Accuracy (*) Overload protection
60.00A 0.01A
±(2.2%rdg.+10dgt)
600AACrms
600.0A 0.1A
±(2.0%rdg+8dgt)
(*) Referred to cable inside to the center of clamp jaws
Position sensitivity: ±2.0%rdg