Instructions / Assembly
Table Of Contents
- Part 1 - General Safety Information
 - Part 2 - Before You Start
 - Part 3 - Prepare the Boiler
- A. Locating the Boiler
 - B. Structure
 - C. Leveling
 - D. Clearances for Service Access
 - E. Wall Mounting Considerations
 - F. Wall Mounting Instructions
 - G. Residential Garage and Closet Installations
 - H. Exhaust Vent and Intake Pipe
 - I. Carbon Monoxide Detectors
 - J. Prevent Combustion Air Contamination
 - K. Removing a Boiler from a Common Vent System
 - K. Water Chemistry Requirements*
 - L. Technical Specifications
 
 - Part 4 - Piping
- A. General Plumbing Information
 - B. Relief Valve
 - C. Backflow Preventer
 - D. Potable Expansion Tank
 - E. Circulators
 - F. Hydronic Piping with Circulators, Zone Valves, and Multiple Boilers
 - G. Circulator Sizing
 - H. Check / Control Water Chemistry
 - I. Plumbing
 - J. Fill and Purge Heating System
 - K. Glycol Antifreeze Solutions
 - L. Zoning with Zone Valves
 - M. Zoning with Circulators
 - N. Multiple Boilers
 - O. Applications*
 
 - Part 5 - Venting
 - Part 6 - Condensate Removal
 - Part 7 - Wiring
- A. Installation Must Comply With
 - B. Field Wiring Terminations
 - C. Field Wiring
 - D. Line Voltage Wiring for Standard Boiler
 - E. Alarm Connections
 - F. Low Voltage Connections for Standard Boiler
 - G. Thermostat
 - H. Outdoor Sensor
 - I. Indirect Sensor
 - J. Optional 0-10 Volt Building Control Signal
 - K. Optional UL353 Low Water Cut-Off Interface Kit
 - L. Wiring of Cascade System Communication Bus
 - M. Cascade Master Pump and Sensor Wiring
 - N. Cascade Follower Pump and Sensor Wiring
 
 - Part 8 - Gas Connections
 - Part 9 - Start-Up Preparation
- A. Check / Control Water Chemistry
 - B. Check for Gas Leaks
 - C. Freeze Protection (When Used)
 - D. Fill and Test Water System
 - E. Purge Air from Water System
 - F. Check Thermostat Circuit(s)
 - G. Condensate Removal
 - H. Final Checks Before Starting Boiler
 - I. Setting Up a Single Boiler
 - J. Setting Up a Cascaded System
 - K. Lockout Condition
 - L. Cascade System Programming
 
 - Part 10 - Start-Up Procedure
 - Part 11 - Start-Up Procedures for the Installer
 - Part 12 - Troubleshooting
 - Part 13 - Maintenance
 - Part 14 - Shutdown
 - Part 15 - Installation Checklist
 - Part 16 - Maintenance Report
 - Part 17 - Replacement Parts
 

LP-387 Rev. 011 Rel. 006 Date 6.28.19
31
Friction Loss Equivalent in Piping and Fittings
Fittings or Piping
Equivalent Feet
3” 4” 6”
90 Degree Elbow* 5’ 3’ 3’
45 Degree Elbow 3’ 3’ 2’
Coupling 0’ 0’ 0’
Air Inlet Tee 0’ 0’ 0’
Straight Pipe 1’ 1’ 1’
Concentric Kit 3’ N/A N/A
V Series Vent Kit 1’ 1’ 1’
AL20 4c Vent Terminal 1’ 1’ 1’
Table 11 - *Friction loss for long radius elbow is 1 foot less. NOTE: Consult 
Polypropylene venting instructions for friction loss and pressure drop 
equivalents.
b. For example: If the exhaust vent is 3” in diameter, has two 90
o
elbows, and 10 feet of PVC pipe we will calculate:
Exhaust Vent Equivalent Length = (2x5) + 10 = 20 feet.
Further, if the 3” intake pipe has two 90
o
 elbows, one 45
o
 elbow, 
and 10 feet of PVC pipe, the following calculation applies:
Intake Pipe Equivalent Length = (2x5) + 3 + 10 = 23 feet.
The total equivalent length is 43 feet, well below the maximum.
c. Eort should be made to keep a minimum dierence in 
equivalent length between the exhaust vent and intake pipe.
3. The minimum total equivalent length is 16 feet.
F. Longer Vent Runs
The maximum total equivalent length can be extended by increasing 
the diameter of both the exhaust vent and intake pipes equally. 
However, the transitions should begin a minimum of 16 equivalent 
feet from the boiler. Transitions should always be made in vertical 
sections of pipe to prevent the condensate from pooling in the vent 
pipe.
On all models EXCEPT the 285 model, the maximum equivalent length 
for increased diameter vent pipes is 275 ft, which includes 16 ft from 
with boiler with a transition total of 259 ft upsize piping for longer vent 
runs. On the 285 model, the maximum equivalent length for increased 
diameter vent pipes is 250 ft., which includes the 16 ft from the boiler 
with a transition total of 234 ft upsize piping for longer vent runs.
Standard 
Vent Connection
Reducing 
Coupling
Increased Vent Size
3” 4” x 3” 4”
4” 6” x 4” 6”
6” 8” x 6” 8”
Table 12 - Vent Run Transition
Do not exceed the maximum lengths for vent pipes. Excessive length 
could result in boiler shutdown and property damage.
G. Exhaust Vent and Intake Pipe Installation
All joints of positive pressure vent systems must be sealed 
completely to prevent leakage of ue products into the living 
space. Failure to do so could result in property damage, serious 
injury, or death.
1. Use only solid PVC, CPVC, or stainless steel pipe or a Polypropylene 
vent system approved for use with Category IV appliances.
ABS pipe material may be used on air inlet piping only.
2. Remove all burrs and debris from joints and ttings.
3. When using PVC or CPVC pipe, all joints must be properly cleaned, 
primed, and cemented. Use only cement and primer approved for 
use with the pipe material. Cement must conform to ASTM D2564 
for PVC and ASTM F493 for CPVC pipe. NOTE: DO NOT CEMENT 
POLYPROPYLENE PIPE.
4. Ensure the vent is located where it will not be exposed to 
prevailing winds.
5. In all roof venting applications, exhaust discharge must point 
away from the pitch of the roof.
6. If the exhaust vent is to be terminated in a walled o area (such 
as a roof with a parapet wall), ensure the exhaust vent terminates 
a minimum of 10’ from nearest wall and extends level with or 
above the top of the wall. This will ensure ue gas does does not 
get trapped and possibly recirculated into the intake air pipe, which 
could contaminate the combustion air.
7. To prevent water leakage, install adequate roof ashing where the 
pipe enters the roof.
8. Do not locate vent over public walkways, driveways, or parking 
lots. Condensate could drip and freeze, resulting in a slip hazard or 
damage to vehicles and machinery.
9. Due to potential moisture build-up, sidewall venting may not 
be the preferred venting option. To save time and cost, carefully 
consider venting installation and location.
10. Horizontal lengths of exhaust vent must slope back towards the 
boiler not less than ¼” per foot to allow condensate to drain from 
the vent pipe.
11. The exhaust vent must terminate where vapors cannot make 
accidental contact with people or pets, or damage shrubs or plants.
12. In vacant chimney applications, install and seal a rain cap over 
existing chimney openings.
13. All piping must be fully supported. Use pipe hangers at a 
minimum of 4 foot intervals to prevent sagging of the pipe where 
condensate may form.
14. Do not use the boiler to support any piping.
15. Ensure the outdoor exhaust vent termination is screened to 
prevent blockage caused by debris or birds.
16. Ensure the outdoor intake pipe termination is screened to 
prevent blockage caused by debris or birds.
17. Maximum Snow Level Determination: These installation 
Failure to provide a minimum total vent length of 16 equivalent feet 
could result in property damage and improper product operation.
E. Exhaust Vent and Intake Pipe Sizing
1. The exhaust vent and intake pipe size is 3” for 55 - 285 models and 
4” for the 399 model.
2. The maximum total equivalent length of exhaust vent and intake 
pipe  should not exceed 200 feet for all models EXCEPT the 285 
model. Total equivalent length for the 285 model should not 
exceed 150 feet.
a. The equivalent length of elbows, tees, and other ttings are 
listed in the Friction Loss Table.
Total maximum equivalent length of increased diameter exhaust 
vent and intake pipe must not exceed the lengths dened in this 
manual. Failure to keep the total equivalent length below the 
maximum lengths determined in this manual will result in faulty 
boiler operation, substantial property damage, serious personal 
injury, or death.
Figure 16 - Extended Vent Runs










