Instructions / Assembly
Table Of Contents
- Part 1 - General Safety Information
- Part 2 - Before You Start
- Part 3 - Prepare the Boiler
- A. Locating the Boiler
- B. Structure
- C. Leveling
- D. Clearances for Service Access
- E. Wall Mounting Considerations
- F. Wall Mounting Instructions
- G. Residential Garage and Closet Installations
- H. Exhaust Vent and Intake Pipe
- I. Carbon Monoxide Detectors
- J. Prevent Combustion Air Contamination
- K. Removing a Boiler from a Common Vent System
- K. Water Chemistry Requirements*
- L. Technical Specifications
- Part 4 - Piping
- A. General Plumbing Information
- B. Relief Valve
- C. Backflow Preventer
- D. Potable Expansion Tank
- E. Circulators
- F. Hydronic Piping with Circulators, Zone Valves, and Multiple Boilers
- G. Circulator Sizing
- H. Check / Control Water Chemistry
- I. Plumbing
- J. Fill and Purge Heating System
- K. Glycol Antifreeze Solutions
- L. Zoning with Zone Valves
- M. Zoning with Circulators
- N. Multiple Boilers
- O. Applications*
- Part 5 - Venting
- Part 6 - Condensate Removal
- Part 7 - Wiring
- A. Installation Must Comply With
- B. Field Wiring Terminations
- C. Field Wiring
- D. Line Voltage Wiring for Standard Boiler
- E. Alarm Connections
- F. Low Voltage Connections for Standard Boiler
- G. Thermostat
- H. Outdoor Sensor
- I. Indirect Sensor
- J. Optional 0-10 Volt Building Control Signal
- K. Optional UL353 Low Water Cut-Off Interface Kit
- L. Wiring of Cascade System Communication Bus
- M. Cascade Master Pump and Sensor Wiring
- N. Cascade Follower Pump and Sensor Wiring
- Part 8 - Gas Connections
- Part 9 - Start-Up Preparation
- A. Check / Control Water Chemistry
- B. Check for Gas Leaks
- C. Freeze Protection (When Used)
- D. Fill and Test Water System
- E. Purge Air from Water System
- F. Check Thermostat Circuit(s)
- G. Condensate Removal
- H. Final Checks Before Starting Boiler
- I. Setting Up a Single Boiler
- J. Setting Up a Cascaded System
- K. Lockout Condition
- L. Cascade System Programming
- Part 10 - Start-Up Procedure
- Part 11 - Start-Up Procedures for the Installer
- Part 12 - Troubleshooting
- Part 13 - Maintenance
- Part 14 - Shutdown
- Part 15 - Installation Checklist
- Part 16 - Maintenance Report
- Part 17 - Replacement Parts

LP-387 Rev. 011 Rel. 006 Date 6.28.19
33
WHICHEVER IS GREATER
12" OVER MAXIMUM
SNOW LEVEL OR 24"
LP-445-G
06/23/15
SCREEN INTO
INSERT INLET/EXHAUST
STRAIGHT COUPLING
INSERT INLET/EXHAUST
SCREENS INTO
EACH END OF TEE
AND COUPLING (EXHAUST)
STRAIGHT
COUPLING
RIGHT SIDE VIEW
TWO PIPE ROOF VENTING WITH TEE (INTAKE)
TEE
EXHAUST
VENT
INTAKE AIR
VENT
24" MIN.
TWO PIPE SIDEWALL VENTING WITH TEE (INTAKE)
AND COUPLING (EXHAUST)
Figure 17 - Two Pipe Roof and Sidewall Venting
Take extra precaution to adequately support the weight of vent
pipes terminating through the roof. Failure to properly support roof
terminated piping could result in property damage, serious injury,
or death.
GREATER (TYP)
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
OR GRADE, WHICHEVER IS
VENT KIT
EXHAUST
ANTICIPATED SNOW LEVEL
EXTERIOR WALL
06/23/15
LP-505-A
Sidewall Venting
with Kit
05/26/15
LP-505-C
INTAKE
IMPORTANT:
EXHAUST
INTAKE LEG MUST
BE FACING UP
CONCENTRIC VENT KIT
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW
LEVEL OR GRADE, WHICHEVER IS
GREATER (TYP.)
1" MIN.
Sidewall Venting with
Concentric Kit
12" OVER MAXIMUM SNOW
LEVEL OR 24" - WHICHEVER
IS GREATER
05/26/15
LP-505-C
CONCENTRIC VENT KIT
POSITION TO PREVENT CONDENSATE BLOCKAGE
NOTE: EXTENDED VENT RUNS WHEN
TRANSITIONING TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE IN A VERTICAL
Roof Venting
with
Concentric
Vent Kit
Figure 18 - Venting with Optional Kits (NOT INCLUDED WITH THE BOILER)
NOTE: These drawings are meant to demonstrate system venting only.
The installer is responsible for all equipment and detailing required by
local codes.
All vent pipes must be glued, properly supported, and the exhaust
pitched a minimum of 1/4” per foot back to the boiler to allow
drainage of condensate. When placing support brackets on vent
piping, the rst bracket must be within 1 foot of the boiler and the
balance of 4 foot intervals on the vent pipe. Venting must be readily
accessible for visual inspection from the rst three feet from the
boiler.










