ELITE FT INSTALLATION START-UP MAINTENANCE PARTS Models* EFT-55 / 80 / 110 / 155 / 199 / 285 / 399 *A suffix of “LP” denotes propane gas *A suffix of “N” denotes natural gas This manual must only be used by a qualified heating installer/service technician. Read all instructions in this manual before installing. Perform steps in the order given. Failure to comply could result in substantial property damage, severe personal injury, or death.
IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE. DO NOT STORE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER BOILER. WHAT TO DO IF YOU SMELL GAS Do not try to light any boiler. Do not touch any electrical switch. Do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important product information. DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Code for the installation of Heat Producing Boilers (latest version), from American Insurance Association, 85 John Street, New York, NY 11038. The latest version of the National Electrical Code, NFPA No. 70. NOTE: The gas manifold and controls met safe lighting and other performance criteria when the boiler underwent tests specified in ANSI Z21.13 – latest edition.
TABLE OF CONTENTS PART 1 – GENERAL SAFETY INFORMATION .......................................................................................................................... 8 A. PRECAUTIONS .......................................................................................................................................................................... 8 B. IMPROPER COMBUSTION .......................................................................................................................
N. ZONING WITH CIRCULATORS ............................................................................................................................................... 32 O. MULTIPLE BOILERS ............................................................................................................................................................... 32 PART 6 – VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL ........................................................................... 33 A. GENERAL ......
D. FILL AND TEST WATER SYSTEM .......................................................................................................................................... 61 E. PURGE AIR FROM WATER SYSTEM ..................................................................................................................................... 62 F. CHECK THERMOSTAT CIRCUIT(S) .......................................................................................................................................
PART 1 – GENERAL SAFETY INFORMATION A. PRECAUTIONS This boiler is for indoor installations only. Clearance to combustible materials: 6” top, bottom, and sides, 0” back. Left side has all boiler mechanical connections. Front must have room for service, 24” recommended. (A combustible door or removable panel is acceptable front clearance.) This boiler has been approved for closet installation. Do not install this boiler directly on carpeting. For installation on combustible flooring.
Do not use “homemade cures” or “boiler patent medicines”. Substantial property damage, damage to boiler, and/or serious personal injury may result. Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen from make-up water can cause internal corrosion in system components. Leaks in the boiler or piping must be repaired at once. F.
PART 2 – BEFORE YOU START A.
Condensation Collection System – This boiler is a high efficiency boiler, and will produce condensate. The collection system has a float switch which monitors the condensation level and prevents condensation from backing up into the combustion system. Inside the collection system there is a built in trap which seals the combustion system from the connected drain. This condensate should be neutralized to avoid damage to the drainage system or piping.
Never close existing ventilation openings The service life of the boiler’s exposed metallic surfaces, such as the casing, as well as internal surfaces, such as the heat exchanger, are directly influenced by proximity to damp and salty marine environments. In such areas, higher concentration levels of chlorides from sea spray coupled with relative humidity can lead to degradation of the heat exchanger and other boiler components.
Figure 1 – Required Clearances Space must be provided with combustion/ventilation air openings correctly sized for all other boilers located in the same space as the boiler. The boiler cover must be securely fastened to prevent it from drawing air from the mechanical room. This is particularly important if the boiler is in a room with other boilers. Failure to comply with the above warnings could result in substantial property damage, severe personal injury, or death.
SPECIFICATIONS AND DIMENSIONS Figure 2 – LP-387-K
D. RESIDENTIAL GARAGE, CLOSET, AND ALCOVE INSTALLATIONS Check with your local Authority Having Jurisdiction for requirements when installing boiler in a garage, closet, or alcove. Please read the entire manual before attempting installation. Failure to properly take factors such as boiler venting, piping, condensate removal, and wiring into account before installation could result in wasted time, money, and possible property damage and personal injury.
You must ensure that intake air will not contain any of the contaminants listed in Table 2. For example, do not pipe intake vent near a swimming pool. Avoid areas subject to exhaust fumes from laundry facilities. These areas always contain contaminants. Contaminated air will damage the boiler, resulting in possible substantial property damage, severe personal injury, or death. NOTE: DAMAGE TO THE BOILER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY WARRANTY.
Figure 4 – Pallet with Mounting Bracket Affixed Figure 5 –Boiler Mounted to Bracket B. WALL MOUNTING CONSIDERATIONS These boilers are wall mounted. Use only the wall mounting instructions included in this manual. Ensure the wall that the boiler is intended to be mounted on is comprised of cement, brick, block, or wooden studs spaced 16” apart from center.
b. The provided mounting bracket must be mounted directly to the center of at least 2 studs using standard steel or stainless steel ¼” x 2 ½” lag bolts for all models. Be sure the bracket is level and mark the hole location of the bracket height and horizontal stud location. Ensure the marked holes are located in the center of the building frame (studs). c. For all EFT models, 2 ½” is the minimum lag bolt length if the bracket is directly on stud.
Never use dielectric unions or galvanized steel fittings when connecting to a stainless steel storage tank or boiler. Failure to follow this instruction can lead to premature failure of the boiler system. Such failures ARE NOT covered by warranty. Plumbing of this product should only be done by a qualified, licensed plumber in accordance with all local plumbing codes. The boiler may be connected to a storage tank to supply domestic hot water.
D. SYSTEM WATER PIPING METHODS EXPANSION TANK AND MAKE-UP WATER 1. Ensure that the expansion tank is designed and sized to correctly handle system water volume and temperature. For sizing information, refer to expansion tank manufacturer’s sizing guidelines or the latest ASHRAE expansion tank sizing standards. Expansion tanks must be sized according to total system volume. This includes all length of pipe, all fixtures, boilers, etc.
additional requirements. If the boiler supplies hot water to heating coils in air handler units, flow control valves or other devices must be installed to prevent gravity circulation of boiler water in the coils during the cooling cycle. Chilled water medium must be piped in parallel with, and isolated from, the boiler. Freeze protection for new or existing systems must use glycol that is specifically formulated for this purpose.
Figure 7 – Near Boiler Piping* – NOTE: This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. *Top / Bottom Supply / Return Connections available on EFT-155, EFT-199, EFT-285, and EFT-399 Models ONLY NOTE: In piping applications utilizing a single zone, it is recommended that the installer use flow / check valves with weighted seats at or near the boiler to prevent gravity circulation.
Figure 8 – Piping Symbol Legend
Figure 9 – Standard Piping with Zone Valves and DHW Priority - NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4. The minimum pipe size for connecting a SuperStor indirect water heater is 1” 5.
Figure 10 - Standard Piping with Pumps and DHW Priority - NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4. The minimum pipe size for connecting a SuperStor indirect water heater is 1” 5.
Figure 11 – Primary/Secondary Boiler Piping – Zone Valves and DHW Priority – Outdoor Reset - NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 12 – Primary/Secondary Boiler Piping – Pumps and DHW Priority – Outdoor Reset - NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 13 – Multiple Boilers – Primary/Secondary Piping – Circulators - NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
H. PIPING INSTALLATION This boiler should not be operated as a potable hot water heater. It should not be used as a direct hot water heating device. Basic steps are listed below that will guide you through the installation of the boiler. 1. Connect the system return marked “Boiler Return”. 2. Connect the system supply marked “Boiler Supply”. 3. Install a purge and balance valve or shut off valve and drain on the system return to purge air out of each zone. 4.
The chart below represents the various system design temperature rise through the boiler along with their respective flows and friction loss, which will aid in circulator selection. Table 5 – Boiler Flow Rates In addition, the heat exchanger has a minimum total water volume that must be taken into account when sizing the circulator. These minimum water volumes are listed in Table 6 below.
ACIDITY CONDUCTIVITY CHLORIDE IRON COPPER SODIUM HARDNESS 6 to 8 pH Less than 400 uS/cm at 25oC Less than 100 ppm Less than 0.5 mg/L Less than 0.1 mg/L Less than 20 mg/L Less than 7 Grains Table 8 – Water Quality Requirements Clean system to remove sediment* 1. You must thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be damaged by buildup or corrosion due to sediment. 2.
For installations that incorporate standing iron radiation and systems with manual vents at the high points, follow the previous section and, starting with the nearest manual air vent, open the vent until water flows out. Then close the vent. Repeat the procedure, working your way toward the furthest air vent. It may be necessary to install a basket strainer in an older system where larger amounts of sediment may be present. Annual cleaning of the strainer may be necessary.
PART 6 – VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL The boiler must be vented as detailed in this Venting Section. Ensure exhaust vent and intake piping complies with these instructions regarding vent system. Inspect finished exhaust vent and intake piping thoroughly to ensure all joints are well secured, airtight, and comply with all applicable code requirements, as well as with the instructions provided in this manual.
B. APPROVED MATERIALS FOR EXHAUST VENT AND INTAKE PIPE Item Exhaust vent or Intake pipe and fittings Pipe cement/primer APPROVED EXHAUST VENT AND INTAKE PIPE MATERIAL Standards for Installation in: Material United States Canada PVC schedule 40/80 ANSI/ASTM D1785 PP, CPVC, and PVC venting must be ULC-S636 Certified. PVC-DWV* ANSI/ASTM D2665* IPEX is an approved CPVC schedule 40/80 ANSI/ASTM F441 manufacturer in Canada, supplying vent material listed to Polypropylene ULCS636 ULC-S636.
You must not use “B” vent in an exhaust application. “B” vent is for intake applications ONLY. Using “B” vent in an exhaust application will result in serious injury or death. Figure 14 - NOTE: Drawing is meant to demonstrate system venting ONLY. D. EXHAUST VENT AND INTAKE PIPE LOCATION NOTE: SEE ADDITIONAL REQUIREMENTS FOR MASSACHUSETTS IN THE BACK OF THIS MANUAL. 1. Determine exhaust vent location: Total length of vent may not exceed the limits specified in Part 6.
The building owner is responsible for keeping the exhaust and intake terminations free of snow, ice, or other potential blockages, as well as scheduling routine maintenance. Failure to keep the vent piping terminations clear and properly maintain the boiler could result in property damage, severe personal injury, or death. For each floor containing bedroom(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedrooms, as well as in the room that houses the boiler.
1. Ensure all parts shown in Figure 15-1, Condensate Detail, are included with the condensate trap. If any parts are missing, DO NOT install the trap. Replace the entire condensate assembly. NOTE: Before installation, clean out the condensate collector with water to remove any foreign matter that may block the condensate line. Do not install the condensate assembly if a component is lost or missing. Replace the entire assembly.
Figure 16 - Condensate Piping Suggestions NOTES: 1. Condensate line must be pitched at least 1/4" per foot to properly drain. If this cannot be done, or a very long length of condensate hose is used, you must increase the condensate line to a minimum of 1” ID and place a tee in the line after the condensate neutralizer to properly reduce vacuum lock in the drain line. 2. Plastic pipe should be the only material used for the condensate line.
Figure 17 – Piping Exhaust around Obstructions – Suggested Condensate Removal E. EXHAUST VENT AND INTAKE PIPE SIZING 1. The exhaust vent and intake pipes are 3” for EFT-55/80/110/155/199/285 models, and 4” for the EFT-399. 2. The total equivalent length of exhaust vent and intake pipe should not exceed 200 feet for all models EXCEPT the EFT-285. Total equivalent length for the EFT-285 should not exceed 150 feet. a.
o b. For example: If the 3” exhaust vent has two short 90 elbows and 10 feet of PVC pipe we will calculate: Exhaust Vent Equivalent Length = (2x5) + 10 = 20 feet. o o Further, if the 3” intake pipe has two short 90 elbows, one 45 elbow, and 10 feet of PVC pipe, the following calculation applies: Intake Pipe Equivalent Length = (2x5) + 3 + 10 = 23 feet. The Exhaust Vent Equivalent Length + the Intake Pipe Equivalent Length equal the Total Equivalent Length.
G. DIAGRAMS FOR SIDEWALL VENTING Figure 19 – Sidewall Venting with Tee (Intake) and Coupling (Exhaust) (Standard Equipment) and with Optional Kit NOTE: Vent piping should be 12” over anticipated maximum snow level. NOTE: Drawing is meant to demonstrate system venting ONLY. All vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of ¼” per foot back to the boiler to allow drainage of condensate.
Figure 20 – LP-387-E NOTE: Vent piping should be 12” over anticipated maximum snow level. NOTE: Drawing is meant to demonstrate system venting ONLY. All vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of ¼” per foot back to the boiler to allow drainage of condensate. When placing support brackets on vent piping, the first bracket must be within 1 foot of the boiler and the balance at 4 foot intervals on the vent pipe.
H. DIAGRAM FOR HORIZONTAL VENTING Figure 21 – Horizontal Venting - NOTE: Drawing is meant to demonstrate system venting ONLY. NOTES: A. For every 1” of overhang, the exhaust vent must be located 1” vertical below overhang (overhang means top of building structure and not two adjacent walls [corner of building]). B. Typical installations require 12” minimum separation between bottom of exhaust outlet and top of air intake. C.
I. DIAGRAM FOR UNBALANCED FLUE / VERTICAL VENT Figure 22 – LP-293-T – Unbalanced Flue/Vertical Vent - NOTE: Drawing is meant to demonstrate system venting ONLY. All vent pipes must be glued, properly supported, and the exhaust pitched a minimum of ¼” per foot back to the boiler to allow drainage of condensate. When placing support brackets on vent piping, the first bracket must be within 1’ of the boiler and the balance at 4’ intervals on the vent pipe.
J. DIAGRAM FOR VERTICAL VENTING Figure 23 – LP-293-F NOTE: Vent piping should be 12” over anticipated maximum snow level. NOTE: Drawing is meant to demonstrate system venting ONLY. All vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of ¼” per foot back to the boiler to allow drainage of condensate. When placing support brackets on vent piping, the first bracket must be within 1 foot of the boiler and the balance at 4 foot intervals on the vent pipe.
K. VENTING THROUGH AN EXISTING SYSTEM This boiler may be vented through an existing unused vent system. The inner diameter of the existing vent system is utilized for the combustion air source. Two methods have been approved for such venting: Concentric Venting and Venting as a Chase. Do not install the boiler into a common existing vent with any other boiler. This will cause flue gas spillage or boiler malfunction, resulting in substantial property damage, severe personal injury, or death.
VENT / AIR INLET SIZE 3” 4” Table 13 – Minimum Vent / Chase Sizing MINIMUM EXISTING VENT / CHASE SIZE 5” 7” 2. VENTING AS A CHASE When venting as a chase, follow all instructions included in Part 6 – Venting, of this manual, as well as the previous Concentric Venting section. See Figure 25 for chase venting demonstration. Figure 25 – Existing Venting as Chase NOTE: Drawing is meant to demonstrate system venting ONLY.
L. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE NOTE: This installation is intended for commercial applications. For residential applications, it is recommended to pipe intake combustion air from the outdoors. This boiler requires fresh, uncontaminated air for safe operation and must be installed in a mechanical room where there is adequate combustion and ventilating air. NOTE: To prevent combustion air contamination, see Table 3.
Figure 27 – 1, 27 - 2 NOTE: These drawings are meant to demonstrate system venting only. The installer is responsible for all equipment and detailing required by local codes.
PART 7 – GAS PIPING FAILURE TO FOLLOW ALL PRECAUTIONS IN THIS SECTION COULD RESULT IN FIRE, EXPLOSION, OR DEATH! A. GAS CONNECTION The gas supply shall have a maximum inlet pressure of less than 14" w.c. (3.5 kPa), and a minimum of 3.5" w.c. (.87 kPa). The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop greater than 0.5" (.12 kPa) as stated in the National Fuel Gas Code. This information is listed on the rating label.
4. It is important to support gas piping as the boiler is not designed to structurally support a large amount of weight. 5. Purge all gas lines thoroughly to avoid start up issues with air in the lines. 6. Sealing compound (pipe dope) must be used and approved for gas connections. Apply sparingly, and only to the male threads. Care must be taken when applying compound to prevent blockage or obstruction of gas flow which may affect the operation of the boiler.
DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is factory-set for the correct outlet pressure and requires no field adjustment. Attempts by the installer to adjust or measure the gas valve outlet pressure could result in damage to the valve and cause substantial property damage, severe personal injury, or death. D.
PART 8 – FIELD WIRING To avoid electrical shock, turn off all power to the boiler prior to opening an electrical box within the unit. Ensure the power remains off while any wiring connections are being made. Failure to follow these instructions could result in component or product failure, serious injury, or death. Such product failure IS NOT covered by warranty. ELECTRICAL SHOCK HAZARD - Turn off electrical power supply at service entrance panel before making any electrical connections.
3. Connect the boiler pump as shown in Figure 31 to the terminals marked 1 – (HOT), 2 – (NEUT), and 3 – (GND). The connections shown are suitable for a maximum continuous pump draw of 3 amps at 120 volts. If the pump requires more current or voltage than the 120 volts supplied, an external motor starter or contactor will be required. E. ALARM CONNECTIONS The control includes a dry contact alarm output. This is an SPDT circuit, rated at 5 amps at 120 volts.
NOTE: For correct mounting procedures, follow instructions provided with the sensor. NOTE: If sensor wires are located in an area with sources of potential electromagnetic interference (EMI), the sensor wires should be shielded, or the wires routed in a grounded metal conduit. If using shielded cable, the shielding should be connected to the common ground of the boiler. I. INDIRECT SENSOR There is no connection required if an indirect water heater is not used in the installation. 1.
2. Use standard CAT3 or CAT5 computer network patch cables to connect the communication bus between each of the boilers. These cables are readily available at any office supply, computer, electronic, department or discount home supply store in varying lengths. If you possess the skills you can also construct custom length cables. 3. It is recommended to use the shortest length cable that will reach between the boilers and create a neat installation.
4. Connect the boiler pump to the terminals marked 1 (HOT), 2 (NEUT) and 3 (GND). 5. Connect the system pipe sensor to the terminals marked 10 and 11. NOTE: See Figure 32 for Cascade Master and Follower Wiring detail. N. CASCADE FOLLOWER PUMP AND SENSOR WIRING 1. Connect the boiler pump to the terminals labeled 1 (HOT), 2 (NEUT), and 3 (GND). 2. An alarm bell or light can be connected to the alarm contacts of the follower boiler.
Figure 34 – Cascade Master and Follower Wiring
Figure 35 – Internal Connection Diagram – LP-293-J
PART 9 – START-UP PREPARATION Thoroughly clean and flush any system that has used glycol before installing the boiler. Provide the customer with a material safety data sheet (MSDS) on the fluid used. A. CHECK / CONTROL WATER CHEMISTRY Chemical imbalance of your water can cause severe damage to your boiler and associated equipment, and may also affect efficiency. You may have to have your water quality professionally analyzed to determine whether you need to install a water softener.
Test/replace freeze protection fluid 1. For systems using freeze protection fluids, follow fluid manufacturer’s instructions to verify inhibitor level and that other fluid characteristics are satisfactory. 2. Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time. Follow all fluid manufacturer instructions. NOTE: BOILER FAILURE DUE TO IMPROPER WATER CHEMISTRY IS NOT COVERED BY WARRANTY. B.
5. The system may have residual substances that could affect water chemistry. After the system has been filled and leak tested, verify that water pH and chlorine concentrations are acceptable by sample testing. It is important to purge the system of air to avoid damage to the boiler. E. PURGE AIR FROM WATER SYSTEM IMPORTANT! While commissioning the system, the air vent on top of the boiler must remain fully open to allow the boiler to properly fill.
5. Once the external thermostat circuit wiring is checked and corrected if necessary, reconnect the external thermostat circuit wires to the boiler low voltage terminal strip. Allow the boiler to cycle. G. CONDENSATE REMOVAL 1. The boiler is a high efficiency condensing boiler. Therefore, the boiler has a condensate drain. Condensate fluid is nothing more than water derived from combustion products, similar to that produced by an automobile when it is initially started.
d. Set the Cascade Address parameter 15 to 1 for the first follower, 2 for the second follower, etc., depending on which boiler you are programming. e. Change “CASCADE MODE” parameter to “926 BOILER”. This makes the boiler a follower and enables all data to be transferred between boilers as needed for the system to function to full capability. f. Exit the system menu. NOTE: For the system to operate properly, the temperature set point of the follower must match that of the master boiler. J.
RESET – The RESET button has two functions. – Resets any lockout error code – Returns the user to the default display screen. ENTER MENU CODE 000 ENTER – The ENTER key is used to enter the parameter programming mode. To enter this mode, hold down the ENTER key for more than 4 seconds. The readout will change to: One of the zeroes will be blinking. Use the ▲▼ arrow keys to change the blinking digit to the correct value.
SCREEN CENTRAL HEAT o 180 F DESCRIPTION Function: Adjusts the boiler set point. Default: 180oF (Range: 50oF to 190oF). CENTRAL DIFF SET o 30 F Function: Adjusts the boiler differential set point. Default: 30oF (Range: 5oF to 30oF). DHW SET POINT o 119 F Function: Adjusts the indirect tank set point. Default: 119oF (Range: 70oF to 185oF). DHW DIFF SET POINT o 7 F Function: Adjusts the indirect tank differential set point. Default: 7oF (Range: 1oF to 30oF).
pressing the UP ARROW and decreased by pressing the DOWN ARROW on the display. When done, press ENTER. Setting will stop blinking and you can move on to next setting. Press RESET to exit programming and store settings. Listed below are the boiler settings that can be programmed into the control. SCREEN Function 1 MODE INDIRECT 1 Function 3 DHW TANK MAX TEMP o 180 F 3 Function 6 DESCRIPTION Factory Program Mode This screen indicates that the control is configured correctly. Do not change this setting.
Function 23 CASCADE MODE VISION 3 23 Function 24 CASCADE ROTATION 48 HOURS 24 Function 25 NOT USED NOT USED 25 Function 26 Cascade Mode SYS FREEZE PROT PROTECT OFF 26 NOTE: This parameter is only present if the boiler is a cascade master. Allows the user to set the freeze protection when a system pump is used. Factory Default: OFF. Selection of temperature activates freeze protection. (Range: OFF, -40oF – 104oF).
G. RESETTING THE MAINTENANCE SCHEDULE When the system control flashes MAINTENANCE REQUIRED, it is advisable that you call for service. After the service is performed, reset the schedule for the next required service by using the following steps. Press ENTER on the display for 3 seconds. The Menu code will appear as 000. This does not change. Press ENTER again. SERVICE SCHEDULE RESET will be displayed. Using the right arrow key scroll to the selection of year or hours.
Press the ▼ key once. DHW SET DHW o 119 F o 117 F This screen displays the domestic hot water temperature set point on the top line. The actual temperature measured by the tank or return line sensor (HTP 7250P-325) is displayed on the bottom line.
Press the ▼ key once. This screen displays the ninth oldest lockout fault that occurred in the boiler controller. The top line will alternate between the words ‘FAULT HISTORY’ and the fault encountered. The bottom line displays the date and time the fault occurred. FAULT HISTORY 9 08/28/2009 Fr 5:19A Press the ▼ key once. This screen displays the tenth oldest lockout fault that occurred in the boiler controller. The top line will alternate between the words ‘FAULT HISTORY’ and the fault encountered.
CARBON MONOXIDE (CO%) CARBON DIOXIDE (CO2%) Table 26 MODEL EFT-55 EFT-80 EFT-110 EFT-155 EFT-199 EFT-285 EFT-399 COMBUSTION SETTINGS ON ALL MODELS NATURAL GAS High <150 ppm 8 ½ - 10 ½% IGNITION 3800 3800 3800 4100 3800 4600 4200 ELITE FT FAN SPEEDS MIN 1650 1850 1850 1850 1750 1800 1900 PROPANE LP High <150 ppm 9 ½ - 10 ½% MAX 4050 5000 6050 5400 6050 6050 6950 Table 27 PART 12 – SHUTDOWN A. SHUTDOWN PROCEDURE If the burner is not operating, disconnect the electrical supply.
B. BOILER ERROR When an error condition occurs, the controller will display a description and code on the display readout. These error messages and their recommended corrective actions are described in Section D. C. BOILER FAULT 1. When a fault condition occurs, the controller will illuminate the red “FAULT” indication light and display a fault message in the screen. The alarm output will also activate. Most fault conditions cause the CH pump to run in an attempt to cool the boiler. 2.
Fault Code TT Temperature Blocking TT Demand TEMPER BLOCKING PUMP ON TT This screen indicates a temporary hold on the burner. There is a demand on the boiler, the pump is powered on, but the temperature of the water at the supply sensor is too high for the boiler to ignite. This occurs because the water temperature measured by the supply sensor is higher than the boiler temperature – ignition diff setting.
Fault Code F02 SUPPLY SENSOR F02 PUMP ON Indicates that the supply temperature sensor of the boiler has failed. This is a serious safety issue and the boiler will not restart until the sensor is replaced by a technician and he pushes the RESET button on the display. This situation is indicated by the red light on the display and the flashing word LOCKOUT. During this lockout fault, the pump will be on as indicated on the second line of the display. 1.
Figure 36 – Proper Electrode Spacing Fault Code F10 FLAME LOSS F10 The flame was lost while the boiler was firing 3 times during 1 demand call. The red light will display and the word LOCKOUT will flash. This code indicates a serious safety issue. The boiler will not restart until the cause of flame loss is determined by a technician and he pushes the RESET button on the display. During this lockout fault, the pump will be on as indicated on the second line of the display. 1.
Fault Code F31 PROGRAM ERROR F31 There was an error while programming the control and the memory is corrupt. The boiler control will not function in this state and the pump will be off as indicated on the bottom line. This error only occurs if a technician is programming the control and the programming function fails. The only way to recover from this error is to reprogram the control.
Table 29 PART 14 – MAINTENANCE A. MAINTENANCE PROCEDURES Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of the boiler. The installer must also inform the owner that a lack of proper care and maintenance of the boiler may result in a hazardous condition.
The combustion chamber insulation in this product contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Avoid breathing dust and contact with skin and eyes. Use NIOSH certified dust respirator (N95).
2. Close isolation valves on the return and supply connections to the boilers as shown in the piping diagrams within this manual. Slowly open the ball valves and release pressure into a bucket. Once pressure is released, connect a hose to the water line to flush the boiler. Scale removing solution may be used, but must be approved for use with stainless steel and FDA approved for use in a potable water system. 3. Thoroughly flush the heat exchanger before commissioning the boiler back in service. D.
Do not install the condensate assembly if a component is lost or missing. Replace the entire assembly. Failure to follow this warning could result in property damage, serious personal injury, or death. 6. Fill the condensate trap with fresh water prior to reassembly on the boiler. 7. Slide the condensate trap adapter onto the drain tube until the holes line up with the groove. 8. Insert stainless steel hitch pin to lock condensate adapter to the drain tube. 9.
EFT-55 / 80 / 110 PARTS BREAKDOWN Figure 38 - Replacement Parts - LP-387-J
EFT-55 / 80 / 110 PARTS BREAKDOWN Figure 39 – Replacement Parts - *#20 – Switch on the Left is the Blocked Flue Pressure Switch, Switch on the Right is the Blocked Condensate Pressure Switch – Both share same Part Number
EFT-155 / 199 / 285 / 399 PARTS BREAKDOWN Figure 40 - Replacement Parts - LP-387-KK
EFT-155 / 199 / 285 / 399 MODEL PARTS BREAKDOWN Figure 41 - Replacement Parts - LP-387-JJ – EFT-155 - 399 Models
BOILER START-UP REPORT LIGHT OFF ACTIVITIES 1) Fill the heating system 2) Check gas pipe 3) Check combustion 4) Verify system operation 5) Record ionization current 6) Indirect water heater 7) Convert the boiler 8) Record system settings Notes: DATE COMPLETED ________________ Check all piping and gas connections, verify all are tight Pressurize system (12 – 15 psi) Add water to prime condensate cup Percentage of glycol in system (0 – 50%) Verify near boiler piping is properly supported Leak test u
the boiler. Installer must also inform the owner that the lack of proper care and maintenance of the boiler may result in a hazardous condition.
MAINTENANCE NOTES
HTP CUSTOMER INSTALLATION RECORD FORM The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim. After reading the important notes at the bottom of the page, please also sign this document.