6.3.7.3 PID-SSC Running Parameters
Parameter
Description
Operation mode
Specifies the current working mode of the PID module.
Set this parameter to Manual during commissioning after deployment or
fault locating. In this case, the PID-SSC delivers the output voltage
based on the value of the commissioned output voltage.
Set this parameter to Automatic after ensuring that the PID module
works normally.
Output voltage (manual)
Specifies the output voltage when the PID module works in commissioning
mode. It is recommended that Output voltage (manual) be set to a value
greater than 250 V.
6.3.8 Setting Power Meter Parameters
6.3.8.1 Setting DL/T645 Power Meter Parameters
Procedure
Step 1 Set access parameters and click Add Devices.
Figure 6-22 Setting access parameters
Parameter
Description
Device Type
Set this parameter to Power Meter.
Comm. Protocol
Set this parameter to DL/T645.
Port number
Set this parameter to the serial number of the COM port
connected to the power meter.
Address
Set this parameter to the communication address of the power
meter.
Table ID
Set this parameter to the meter ID.