Transparent Transmission Mode
Step 1 Set IEC103 parameters and click Submit.
Figure 6-32 Setting IEC103 parameters
Parameter
Description
IEC103 port No.
Set this parameter based on the COM port connected to the
device.
IEC103 address
Set this parameter to the IEC103 device address.
IEC103 IP
Set this parameter to the IP address of the management
system.
Step 2 Choose Settings > Other Parameters and check that Data forwarding is set to Enable.
If Data forwarding is set to Enable, the SmartLogger transparently transmits information
about unconnected devices to the management system without parsing device data.
If Data forwarding is set to Disable, the SmartLogger does not transmit information
about unconnected devices to the management system.
----End
Parsing Mode
The SmartLogger can connect to third-party devices that support IEC103, such as the relay
protection or monitoring device like the transformer substation. The protocol information
points vary depending on vendors. Therefore, you need to obtain a protocol information file
in .cfg format from Huawei and import the file into the SmartLogger for successfully
connecting to a custom device.
The supported device types are IEC103 device 1 to IEC103 device 5. The corresponding
configuration file names are iec103_equip_custom_1.cfg to iec103_equip_custom_5.cfg.
Multiple devices of the same type can be connected.
Step 1 Configure a protocol information point file in .cfg format and import the file to the
SmartLogger.