Figure 6-35 Device monitoring
Tab
Function
Description
Running Info.
View the running
information about the
IEC103 device.
N/A
Teleindication
View the device status, such
as the switch status.
N/A
Telemetering
View the real-time analog
data of the device, such as
the voltage.
N/A
Telecontrol
Set the status control
parameters, such as the
parameters for turning on or
off switches.
Set the parameters on the
tab page as required.
Teleadjust
Set analog parameters, for
example, set voltage
protection parameters.
Set the parameters on the
tab page as required.
----End
6.3.12 Setting Parameters for a Custom Device
Context
The SmartLogger can connect to third-party devices supporting the Modbus-RTU protocol,
such as the transformer substation and EMI. The protocol information points vary depending
on vendors. Therefore, you need to configure a protocol information file in .cfg format and
import the file into the SmartLogger for successfully connecting to a custom device.
The supported device types are custom device 1 to custom device 10. The corresponding
configuration file names are modbus_equip_custom_1.cfg to
modbus_equip_custom_10.cfg. Multiple devices of the same type can be connected.
Procedure
Step 1 Configure a protocol information point file in .cfg format and import the file to the
SmartLogger.