6 WebUI Operations
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
137
Table 6-5 DRM requirements
Mode
Corresponding
Port on the
SmartLogger
Requirements
Remarks
DRM0
AI2–AI4
When S0 is turned on, the
inverters shut down.
When S0 is turned off, the
inverters are connected to the
power grid.
N/A
DRM5
DI1
When S5 is turned on, the inverters
do not output active power.
When two or
more DRM
modes are used
at the same
time, the
strictest
requirement
must be met.
DRM6
DI2
When S6 is turned on, the output
active power of the inverters does not
exceed 50% of the rated power.
DRM7
DI3
When S7 is turned on, the output
active power of the inverters does not
exceed 75% of the rated power, and
the inverters consume the maximum
reactive power.
DRM8
DI4
When S8 is turned on, the output
active power of inverters recovers.
NOTE
The inverters output active power based
on the percentage set on the
SmartLogger.
Procedure
Step 1 Click Settings and ensure that Active Power Control Mode is set to No limit, Reactive
Power Control Mode is set to No output, and connection port for Remote Shutdown is set
to No.
Step 2 Set DRM parameters and click Submit.
Figure 6-49 Setting DRM parameters