User's Manual
Table Of Contents
- About This Document
- Contents
- 1 Safety Information
- 2 Product Overview
- 3 Device Installation
- 4 Cable Connections
- 4.1 Connecting Cables to the SmartLogger
- 4.1.1 Preparing Cables
- 4.1.2 Connecting a PE Cable
- 4.1.3 Connecting an RS485 Communications Cable
- 4.1.4 Connecting an MBUS Cable
- 4.1.5 Connecting a DI Signal Cable
- 4.1.6 Connecting the Output Power Cable
- 4.1.7 Connecting the AI Signal Cable
- 4.1.8 Connecting the DO Signal Cable
- 4.1.9 Connecting the Ethernet Cable
- 4.1.10 Connecting Fiber Jumpers
- 4.1.11 Installing a SIM Card and a 4G Antenna
- 4.1.12 Connecting the 24 V Input Power Cable
- 4.2 Connecting Cables to the SmartModule
- 4.2.1 Preparing Cables
- 4.2.2 Connecting the PE Cable
- 4.2.3 Connecting the Ethernet Cable
- 4.2.4 Connecting the 12 V Power Input Cable
- 4.2.5 Connecting the RS485 Communications Cable
- 4.2.6 Connecting the DI Signal Cable
- 4.2.7 Connecting the Output Power Cable
- 4.2.8 Connecting the AI Signal Cable
- 4.2.9 Connecting the PT Signal Cable
- 4.2.10 Connecting the 24 V Power Input Cable
- 4.1 Connecting Cables to the SmartLogger
- 5 System Operation
- 6 WebUI Operations
- 6.1 Introduction to WebUI
- 6.2 Device Commissioning
- 6.3 Parameter Settings
- 6.3.1 Setting User Parameters
- 6.3.2 Setting Parameters for Connecting to the Management System
- 6.3.3 Setting RS485 Communications Parameters
- 6.3.4 Setting Parameters for the Slave SmartLogger
- 6.3.5 Setting MBUS Parameters
- 6.3.6 Setting SUN2000 Parameters
- 6.3.7 Setting PID Module Parameters
- 6.3.8 Setting Power Meter Parameters
- 6.3.9 Setting EMI Parameters
- 6.3.10 Setting STS Parameters
- 6.3.11 Setting IEC103 Device Parameters
- 6.3.12 Setting Parameters for a Custom Device
- 6.3.13 Setting IEC104 Device Parameters
- 6.4 Power Grid Scheduling
- 7 Device Maintenance
- 8 FAQ
- 8.1 How Do I Connect the SmartLogger to the SUN2000 App or FusionSolar App?
- 8.2 How Do I Set FTP Parameters?
- 8.3 How Do I Set Email Parameters?
- 8.4 How Do I Change the SSID and Password of the Built-in WLAN?
- 8.5 How Do I Use DI Ports?
- 8.6 How Do I Use DO Ports?
- 8.7 How Do I Use the USB Port?
- 8.8 How Do I Change a Device Name?
- 8.9 How Do I Change the Communications Address?
- 8.10 How Do I Export Inverter Parameters?
- 8.11 How Do I Clear Alarms?
- 8.12 How Do I Enable the AI1 Port to Detect SPD Alarms?
- 8.13 Which Models of Power Meters and EMIs Are Supported by the SmartLogger?
- 8.14 How Do I Check the SIM Card Status?
- 9 Technical Specifications
- A Product User Lists
- B Domain Name List of Management Systems
- C Acronyms and Abbreviations
SmartLogger3000
User Manual
7 Device Maintenance
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
142
No.
Fault
Cause
Suggestions
5
The EMI fails
in
communicatio
n.
1. The RS485 communications cable
between the EMI and the
SmartLogger is connected incorrectly,
loose, or disconnected.
2. The EMI is not powered on.
3. The EMI and SmartLogger use
different RS485 communications
parameter settings.
4. The EMI parameters are incorrectly
set.
1. Check the cable connection. If the
cable is loose or disconnected,
reconnect it firmly.
2. Power on the EMI.
3. Check that the RS485
communications parameters of the
EMI are correctly.
4. Log in to the WebUI and ensure that
the EMI parameters are set correctly.
6
The
SmartLogger
cannot
communicate
with the
management
system.
1. The SmartLogger is not connected to
the PC, or the cable is loose or
disconnected.
2. The parameters of the wired or
wireless network are incorrectly set.
3. The management system parameters
are incorrectly set.
1. Check that the Ethernet port of the
SmartLogger is correctly connected
to the PC or a router.
2. Check that the parameters of the
wired or wireless network are set
correctly.
3. Check that the management system
parameters are correctly set.
7
The
communicatio
n for RS485
networking
failed.
1. The RS485 communications cable is
incorrectly connected, loose, or
disconnected.
2. The SmartLogger is not powered on.
3. The RS485 communications
parameters are incorrectly set.
1. Terminal block connection: Check
that the RS485 communications
cable is connected to the correct port
of the terminal block.
2. RJ45 network port connection:
Check that the RJ45 connector is
properly crimped and that each wire
is connected to the correct pin.
3. Check that the RS485 ports of other
devices are connected to the correct
ports of the SmartLogger.
4. Check the RS485 cable connection.
If the cable is loose, disconnected, or
reversely connected, reconnect it
firmly.
5. Power on the SmartLogger and its
connected device.
6. Check the RS485 communications
parameter settings.
7. Contact the dealer or Huawei
technical support.
8
The 4G
communicatio
n is abnormal.
1. The SIM card is not inserted or it is in
arrears or damaged.
2. The 4G antenna is not tightened or is
damaged.
3. The management system parameters
and wireless network parameters are
incorrectly set.
4. The SIM card registration failed.
1. Insert or replace the SIM card.
2. Tighten or replace the 4G antenna.
3. Check that the management system
parameters and wireless network
parameters are set correctly.
4. Contact the SIM card carrier or
Huawei technical support.