User's Manual

Table Of Contents
SmartLogger3000
User Manual
7 Device Maintenance
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
144
Alarm
ID
Alarm
Name
Alarm
Severity
Alarm
Sub-ID
Cause
Suggestions
1105
Device
Address
Conflict
Major
1
The
SmartLogger
RS485 address
conflicts with
the physical
address (RS485
address) or
logical address
for the
connected
southbound
device.
If the SmartLogger RS485 address
conflicts with the communications
address for the connected southbound
device, choose Settings > Modbus TCP
and change the SmartLogger address, or
choose Maintenance > Device
Mgmt. > Connect Device and change
the southbound device address. If the
southbound device is a solar inverter,
you can change its address on the app.
If the SmartLogger RS485 address
conflicts with the logical address for the
connected southbound device, choose
Settings > Modbus TCP and change
the SmartLogger address.
1106
AC SPD
Fault
Major
1
The SPD in the
smart array
controller is
faulty.
Check whether the cable to the SPD in
the smart array controller is loose,
disconnected, or reversely connected. If
so, reconnect the cable firmly.
Check whether the SPD in the smart
array controller is faulty. If so, replace
the faulty SPD.
1107–1
110
DI1
user-defi
ned
alarm to
DI4
user-defi
ned
alarm
Major
1
The dry contact
signal from the
peripheral to the
corresponding
DI port of the
SmartLogger is
abnormal.
Check the DI port cable connection. If
the cable is loose, disconnected, or
reversely connected, reconnect it firmly.
Check that the relevant device works
properly.
1111–1
114
M1.DI1
user-defi
ned
alarm to
M1.DI4
user-defi
ned
alarm
Major
1
The dry contact
signal from the
peripheral to the
corresponding
DI port of the
SmartModule is
abnormal.
Check the DI port cable connection. If
the cable is loose, disconnected, or
reversely connected, reconnect it firmly.
Check that the relevant device works
properly.
1115
24 V
Power
Failure
Major
1
The 24 V power
supply in the
smart array
controller is
faulty.
1. Check whether the cable to the 24 V
power supply in the smart array
controller is loose, disconnected, and
connected in reverse. If so, reconnect
the cable securely.
2. Check whether the 24 V power supply
in the smart array controller is faulty.
Replace the faulty power module.