User's Manual

Table Of Contents
SmartLogger3000
User Manual
4 Cable Connections
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
47
Figure 4-10 Connecting an Ethernet cable
(1) White-and-orange
(2) Orange
(3) White-and-green
(4) Blue
(5) White-and-blue
(6) Green
(7) White-and-brown
(8) Brown
----End
4.1.10 Connecting Fiber Jumpers
Context
The SmartLogger can connect to devices such as the access terminal box through optical
fibers.
Procedure
Step 1 Insert an optical module into the SFP1 or SFP2 port of the SmartLogger. If there are two
modules, insert one into each port.
Optical modules are optional. Configure the 100M or 1000M optical module based on the
peer port of the optical switch. The optical module should use the SFP or eSFP
encapsulation. The transmission distance supported by the 100M optical module should be
greater than or equal to 12 km, and the transmission distance supported by the 1000M
optical module should be greater than or equal to 10 km.
When inserting an optical module into the SFP1 port, verify that the side with a label faces
upward. When inserting an optical module into the SFP2 port, verify that the side with a
label faces downward.
Step 2 Connect the fiber jumpers delivered with the optical module to the ports of the optical
module.