User's Manual

Table Of Contents
SmartLogger3000
User Manual
4 Cable Connections
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
50
Figure 4-13 Connecting the input power cable
----End
4.2 Connecting Cables to the SmartModule
4.2.1 Preparing Cables
Type
Recommended Cable Specifications
PE cable
Outdoor copper-core cable with a cross-sectional area of 4–6 mm
2
or 12–10 AWG
Network cable
The cable is delivered with the SmartModule and is 0.35 m long. If the delivered
network cable is too short, you are advised to prepare a network cable of Cat 5e or
higher specifications and shielded RJ45 connectors.
12 V power input
cable
The cable is delivered with the SmartModule and is 0.5 m long.
RS485
communications
cable
Two-core or multiple-core cable with a cross-sectional area of 0.2–2.5 mm
2
or 24–14
AWG
DI signal cable
Two-core or multiple-core cable with a cross-sectional area of 0.2–1.5 mm
2
or 24–16
AWG
Output power cable
AI signal cable
PT signal cable
For details about the cables and cable connection operations, see the documents
delivered with the PT100/PT1000.
(Optional) 24 V
power input cable
Two-core cable with a cross-sectional area of 0.2–1.5 mm
2
or 24–16 AWG