6 WebUI Operations
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
79
Figure 6-10 Setting Modbus TCP parameters
Parameter
Description
Link setting
Modbus TCP is a universal standard protocol used to connect
to a third-party management system. Because there is no
security authentication mechanism, data transmitted by
Modbus TCP is not encrypted. To reduce network security
risks, the function of connecting to a third-party management
system using Modbus TCP is disabled by default. This
protocol can transmit the running data and control commands
of PV plants, which may cause user data breach and control
permission theft. Therefore, exercise caution when using this
protocol. Users are liable for any loss caused by the use of
this protocol to connect to a third-party management system
(non-secure protocol). Users are advised to take measures at
the PV plant level to reduce security risks, or use Huawei
management system to mitigate the risks.
To use this function, set this parameter to Enable(Limited) or
Enable(Unlimited).
If this parameter is set to Enable(Limited), the
SmartLogger can connect to a maximum of five preset
third-party management systems.
If this parameter is set to Enable(Unlimited), the
SmartLogger can connect to a maximum of five
third-party management systems with a valid IP address.
Client N IP Address
NOTE
N is 1, 2, 3, 4, or 5.
If Link setting is set to Enable(Limited), set this parameter
based on the IP address of the third-party management
system.
Address mode
The value can be Comm. Address or Logical address.
If the communications address of the device connected to the
SmartLogger is unique, you are advised to select Comm.
Address. In other cases, you must select Logical address.
SmartLogger address
Set this parameter to the communication address of the
SmartLogger.
Method 3: When the SmartLogger connects to a third-party management system over
IEC104, set IEC104 parameters and click Submit.