6 WebUI Operations
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
83
Parameter
Description
Wakeup period
Specifies the wakeup period for the night
silent mode.
Records
The SmartLogger supports exporting of MBUS and RS485 communication packets.
Set Choose port and click Start to start packet recording. Then, click Export to stop packet
recording and export the packets.
Parameter
Description
Choose port
Specifies the port for recording packets.
6.3.4 Setting Parameters for the Slave SmartLogger
Step 1 Log in to the slave SmartLogger WebUI, set Modbus TCP parameters, and click Submit.
Figure 6-13 Setting Modbus TCP parameters
Parameter
Description
Link setting
Set this parameter to Enable(Limited).
Client N IP Address
Set this parameter to the IP address of the master
SmartLogger.
Address mode
The value can be Comm. Address or Logical address.
If the communications address of the device connected to the
SmartLogger is unique, you are advised to select Comm.
Address. In other cases, you must select Logical address.
SmartLogger address
Set this parameter to the communications address of the slave
SmartLogger.