6 WebUI Operations
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
86
Figure 6-17 Networking settings
Category
Parameter
Description
Running Param.
Baud rate
Retain the default value 115200 for optimal
communications performance.
Anti-crosstalk
Set this parameter to Enable. When the
transformer substation number and winding
number of the solar inverter are the same as
those of the MBUS, or the solar inverter SN is
in the SN list, the solar inverter can connect to
the SmartLogger over an MBUS network.
Network frequency
band
Set this parameter as required.
Box-type
transformer No.
Set this parameter based on the number of the
transformer substation connected to the
SmartLogger.
Winding No.
In multi-split transformer substation scenarios,
set this parameter based on the number of the
winding of the transformer station connected
to the SmartLogger.
Networking
When the SmartLogger communicates
with the solar inverter over MBUS, set
Networking to Enable.
When the SmartLogger communicates
with the solar inverter only over RS485,
set Networking to Disable.
SN List
N/A
Maintain the solar inverter SN list.
You can click Synchronize to synchronize
the transformer substation number and
winding number of the MBUS to the solar
inverters in the SN list.
----End