User's Manual
Table Of Contents
- About This Document
- Contents
- 1 Safety Information
- 2 Product Overview
- 3 Device Installation
- 4 Cable Connections
- 4.1 Connecting Cables to the SmartLogger
- 4.1.1 Preparing Cables
- 4.1.2 Connecting a PE Cable
- 4.1.3 Connecting an RS485 Communications Cable
- 4.1.4 Connecting an MBUS Cable
- 4.1.5 Connecting a DI Signal Cable
- 4.1.6 Connecting the Output Power Cable
- 4.1.7 Connecting the AI Signal Cable
- 4.1.8 Connecting the DO Signal Cable
- 4.1.9 Connecting the Ethernet Cable
- 4.1.10 Connecting Fiber Jumpers
- 4.1.11 Installing a SIM Card and a 4G Antenna
- 4.1.12 Connecting the 24 V Input Power Cable
- 4.2 Connecting Cables to the SmartModule
- 4.2.1 Preparing Cables
- 4.2.2 Connecting the PE Cable
- 4.2.3 Connecting the Ethernet Cable
- 4.2.4 Connecting the 12 V Power Input Cable
- 4.2.5 Connecting the RS485 Communications Cable
- 4.2.6 Connecting the DI Signal Cable
- 4.2.7 Connecting the Output Power Cable
- 4.2.8 Connecting the AI Signal Cable
- 4.2.9 Connecting the PT Signal Cable
- 4.2.10 Connecting the 24 V Power Input Cable
- 4.1 Connecting Cables to the SmartLogger
- 5 System Operation
- 6 WebUI Operations
- 6.1 Introduction to WebUI
- 6.2 Device Commissioning
- 6.3 Parameter Settings
- 6.3.1 Setting User Parameters
- 6.3.2 Setting Parameters for Connecting to the Management System
- 6.3.3 Setting RS485 Communications Parameters
- 6.3.4 Setting Parameters for the Slave SmartLogger
- 6.3.5 Setting MBUS Parameters
- 6.3.6 Setting SUN2000 Parameters
- 6.3.7 Setting PID Module Parameters
- 6.3.8 Setting Power Meter Parameters
- 6.3.9 Setting EMI Parameters
- 6.3.10 Setting STS Parameters
- 6.3.11 Setting IEC103 Device Parameters
- 6.3.12 Setting Parameters for a Custom Device
- 6.3.13 Setting IEC104 Device Parameters
- 6.4 Power Grid Scheduling
- 7 Device Maintenance
- 8 FAQ
- 8.1 How Do I Connect the SmartLogger to the SUN2000 App or FusionSolar App?
- 8.2 How Do I Set FTP Parameters?
- 8.3 How Do I Set Email Parameters?
- 8.4 How Do I Change the SSID and Password of the Built-in WLAN?
- 8.5 How Do I Use DI Ports?
- 8.6 How Do I Use DO Ports?
- 8.7 How Do I Use the USB Port?
- 8.8 How Do I Change a Device Name?
- 8.9 How Do I Change the Communications Address?
- 8.10 How Do I Export Inverter Parameters?
- 8.11 How Do I Clear Alarms?
- 8.12 How Do I Enable the AI1 Port to Detect SPD Alarms?
- 8.13 Which Models of Power Meters and EMIs Are Supported by the SmartLogger?
- 8.14 How Do I Check the SIM Card Status?
- 9 Technical Specifications
- A Product User Lists
- B Domain Name List of Management Systems
- C Acronyms and Abbreviations
SmartLogger3000
User Manual
6 WebUI Operations
Issue 04 (2020-03-11)
Copyright © Huawei Technologies Co., Ltd.
88
Figure 6-19 Setting running parameters
----End
6.3.6.1 Running Parameters
Grid Parameters
Parameter
Description
Grid Code
Set this parameter based on the grid code of the country or region where the
inverter is used and the inverter application scenario.
Isolation settings
Set the working mode of the inverter based on the grounding status at DC
side and the connection to the power grid.
Output mode
Specifies whether the inverter output has a neutral wire based on the
application scenario.
PQ mode
If this parameter is set to PQ mode 1, the maximum AC output power
equals the maximum apparent power. If this parameter is set to PQ mode 2,
the maximum AC output power equals the rated output power.
Automatically start upon grid
recovery
Specifies whether to allow the inverter to automatically start after the power
grid recovers.
Grid connected recovery time
from grid faults (s)
Specifies the time after which the inverter begins restarting after the power
grid recovers.
Grid reconnection voltage upper
limit (V)
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid voltage is higher
than Grid reconnection voltage upper limit, the inverter is not allowed to
reconnect to the grid.
Grid reconnection voltage lower
limit (V)
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid voltage is lower
than Grid reconnection voltage lower limit, the inverter is not allowed to
reconnect to the grid.
Grid reconnection frequency
upper limit (Hz)
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid frequency is
higher than Grid reconnection frequency upper limit, the inverter is not
allowed to reconnect to the grid.