6.3.6.1 Running Parameters
Grid Parameters
Parameter
Description
Grid Code
Set this parameter based on the grid code of the country or region where the
inverter is used and the inverter application scenario.
Isolation settings
Set the working mode of the inverter based on the grounding status at DC
side and the connection to the power grid.
Output mode
Specifies whether the inverter output has a neutral wire based on the
application scenario.
PQ mode
If this parameter is set to PQ mode 1, the maximum AC output power
equals the maximum apparent power. If this parameter is set to PQ mode 2,
the maximum AC output power equals the rated output power.
Automatically start upon grid
recovery
Specifies whether to allow the inverter to automatically start after the power
grid recovers.
Grid connected recovery time
from grid faults (s)
Specifies the time after which the inverter begins restarting after the power
grid recovers.
Grid reconnection voltage upper
limit (V)
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid voltage is higher
than Grid reconnection voltage upper limit, the inverter is not allowed to
reconnect to the grid.
Grid reconnection voltage lower
limit (V)
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid voltage is lower
than Grid reconnection voltage lower limit, the inverter is not allowed to
reconnect to the grid.
Grid reconnection frequency
upper limit (Hz)
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid frequency is
higher than Grid reconnection frequency upper limit, the inverter is not
allowed to reconnect to the grid.