GENERAL PROPERTIES :
Excellent high temperature, low temperature, ozone and weathering resistance,
flame retardant, soldering iron resistant, easy to strip and process, compatible to all common resins and varnishes, flexible.
APPLICATION :
For protected and fixed installation inside electrical equipment, especially suitable for the connection of motor windings,
switchboards, magnets and transformers.
2
1. Conductor : Stranded tin plated copper, class 5 EN 60228
2. Insulation : RADOX 155,
extruded irradiation crosslinked polyolefin
Colours : diverse
1
PRINTING :
0.25--0.5 mm
2
: HUBER+SUHNER SWITZERLAND RADOX 155 ...MM2
0.75--1
mm
2
: HUBER+SUHNER SWITZERLAND RADOX 155 ...MM2 VDE--REG--NR.9331
1.5--4
mm
2
: HUBER+SUHNER SWITZERLAND RADOX 155 ...MM2 VDE--REG--NR.5596
>
6 mm
2
: HUBER+SUHNER SWITZERLAND [Lot No.] RADOX 155 ...MM2 VDE--REG--NR.5596
TECHNICAL DATA:
Temperature range -- 55 ... + 155 °C............................................ .....
Voltages for cross--section
> 0.75 mm
2
:
Rated voltage cond.--earth U
0
600 V AC.................................. ...............
Rated voltage cond.--cond. U 1000 V AC
................................. ................
Maximum permitted operating voltage cond.--earth 720 V AC
................................
Maximum permitted operating voltage cond.--cond. U
m
1200 V AC............... ..............
Maximum permitted operating voltage cond.--earth V
0
900 V DC............... ...............
Maximum permitted operating voltage cond.--cond. 1800 V DC
................................
Test voltage 3500 V AC..............................................................
Voltages for cross--section < 0.75 mm
2
:
Rated voltage cond.--earth U
0
450 V AC.................................. ...............
Rated voltage cond.--cond. U 750 V AC
................................. ................
Maximum permitted operating voltage cond.--earth 480 V AC
................................
Maximum permitted operating voltage cond.--cond. U
m
825 V AC............... ..............
Maximum permitted operating voltage cond.--earth V
0
620 V DC............... ...............
Maximum permitted operating voltage cond.--cond. 1240 V DC
................................
Test voltage 2500 V AC..............................................................
Minimum bending radius Outer diameter < 12 mm 3 x D................. .................
Outer diameter > 12 mm 4 x D....................................... .................
Copyright 2011 Huber + Suhner AG. This document may not be copied nor be passed on to third
parties without our written permission.
Uncontrolled copy when printed (will not be updated].
FAX
Wire+Cable Division
CH--8330 Pfäffikon
+41 (0)44 952 22 11
+41 (0)44 952 26 40
www.hubersuhner.com
The product fulfils the test and specification requirements described in this document for the stated
areas of application and operating conditions. HUBER+SUHNER AG does not expressly or implicitly
guarantee performance under additional or changed conditions. Deviations are to be agreed upon in
writing.

Summary of content (2 pages)