PRODUCT SPECIFICATION
2017 Wall Controls
Rev. 0.2
23Sep2016
Page 13 of 18 Models: K6927, K6731, K6300 Written by:
Charles Mckee
Hunter Fan Company Confidential 13
VII. Regulatory Specifications
A. Units must conform to UL 991 and UL244A as required.
B. FCC part 15
C. IEC 60730-1 Automatic Electrical Controls – General Requirements
D. EMC Performance
IEC 61000-4-2, Electrostatic Discharge Immunity (ESD)
+/- 8KV direct contact
+/- 15KV air discharge
IEC 61000-4-3, Radiated radio-frequency electromagnetic field immunity
Minimum test level of 2 (3V/m)
90-5000 MHz
80% AM at 1kHz Sine Wave
IEC 61000-4-6, Conducted disturbances immunity, induced by radio-
frequency fields
Minimum test level of 2 (3V/m)
90-5000 MHz
80% AM at 1kHz Sine Wave
IEC 60730-1-H.26, Electromagnetic compatibility (EMC) requirements –
Immunity
VIII. Environmental Specifications
A. Operating Conditions: 0ºC to 85ºC for electrical components inside the fan
or control switch housing. A 95% RH must be maintained as well. Note: The
receiver must withstand temperatures up to 85ºC, but the remote has a
requirement of 70ºC.
B. Storage: -40ºC to 70ºC for handheld remote.
C. Storage: -40ºC to 85ºC for receiver.
D. All electronic components must be rated at -40
o
to 85
o
C at least. All
Receivers’ PCBA must be Damp Rated.