Owner's Manual

1. Turn off dispenser and relieve line pressure.
2. Install pipe nipple (if necessary) to achieve proper
ow direction.
3. Apply approved sealant (not Teon tape) thinly to
male threads of hose.
4. Tighten rmly but do not overtighten. Refer to UL 567
for details.
5. Conrm nozzle is properly installed, pressurize the
system and check for leaks.
6. Test nozzle for proper automatic shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
INSTALL DIRECTLY TO THE DISPENSER.
DO NOT OVERTIGHTEN.
DO NOT WRENCH ACROSS COUPLING.
4490
WARNING Designed for use at motor fuel dispensing facilities only.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 1 009037-2 10/2009
INSTALLATION INSTRUCTIONS
IF DRIVE OFF OCCURS
TESTING / MAINTENANCE / INSPECTION
FUEL DISPENSER FLOW RATE TEST PROCEDURE
(For 10 gpm / 37.9 Lpm maximum ow rate standard)
1. Observe a vehicle that is being fueled at the
dispenser's maximum ow rate. Start the stopwatch
when the dispenser indicates 1 gal / 3.8 L dispensed.
2. Carefully measure the time that it takes to dispense
exactly 2*** gal / 7.6 L of fuel.
3. If the time is greater than 11.8*** seconds there is
not a violation.
4. If the time is less than or equal to 11.8*** seconds,
repeat the test for another 2*** gal / 7.6 L into the
same vehicle (if possible). If the second test time
is also less than or equal to 11.8*** seconds, use a
calibrated fuel container to verify the accuracy of the
dispenser meter.
5. When the dispenser meter shows 5 gal / 18.9 L
and the volume dispensed is more than 6 cubic
inches over or under the 5 gal / 18.9 L mark on the
calibrated fuel container, note the amount in the
comment area of the fuels inspection form.
5a. If the volume in the calibrated fuel container
is 5 gal / 18.9 L or greater, record the two test
times and note as a violation.
5b. If the volume in the calibrated fuel container is
less than 5 gal / 18.9 L by more than 6 cubic
inches, conduct the test on another dispenser.
6. Dispose of the fuel following city, state, or federal
regulations.
Conventional Flo-Equalizer™
MODEL 4490
Recommended Installation, Maintenance and
Inspection Instructions
TROUBLESHOOTING GUIDE
Nozzle keeps shutting off or won't dispense... 1. Make sure dispenser is on and activated.
2. Check for blocked lter.
3. Reset the nozzle.
Low ow rate... 1. Check for blocked lter.
2. Remove Flo-Equalizer™ and recheck ow rate.
3. Verify dispenser is not in slow ow rate mode.
4. Check for leak detection failures.
Flow rate above 10 gpm / 37.9 Lpm... 1. Verify Flo-Equalizer™ is being used - either inside
or outside dispenser.
2. Check the Flo-Equalizer™ for debris.
• Inspect the entire dispensing system for damage.
• Check for leaks.
Test nozzle for proper automatic shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
• Check for electrical conductivity.
Daily
• Check for leaks / stains.
Monthly
Check nozzle auto shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
Annually
Check for electrical conductivity.
• Check "remove after" date.
Gallons / Liters Minimum Time
2.0 gal / 7.6 L 11.8 seconds
3.0 gal / 11.4 L 17.7 seconds
4.0 gal / 15.1 L 23.6 seconds
5.0 gal / 18.9 L 29.5 seconds
***Any volume listed in the chart below may be used:
All drive aways, maintenance and inspection activities
must be logged using the serial number of the
individual product.
Apply city, state, or federal testing regulations as
appropriate.
ANY TEST / INSPECTION FAILURE REQUIRES
IMMEDIATE EQUIPMENT REPLACEMENT OR
REMOVAL FROM SERVICE.
MADE IN THE USA

Summary of content (2 pages)