Owner's Manual
1. Turn off dispenser and relieve line pressure.
2. Install pipe nipple (if necessary) to achieve proper
ow direction.
3. Apply approved sealant (not Teon tape) thinly to
male threads of hose.
4. Tighten rmly but do not overtighten. Refer to UL 567
for details.
5. Conrm nozzle is properly installed, pressurize the
system and check for leaks.
6. Test nozzle for proper automatic shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
INSTALL DIRECTLY TO THE DISPENSER.
DO NOT OVERTIGHTEN.
DO NOT WRENCH ACROSS COUPLING.
4490
WARNING Designed for use at motor fuel dispensing facilities only.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 1 009037-2 10/2009
INSTALLATION INSTRUCTIONS
IF DRIVE OFF OCCURS
TESTING / MAINTENANCE / INSPECTION
FUEL DISPENSER FLOW RATE TEST PROCEDURE
(For 10 gpm / 37.9 Lpm maximum ow rate standard)
1. Observe a vehicle that is being fueled at the
dispenser's maximum ow rate. Start the stopwatch
when the dispenser indicates 1 gal / 3.8 L dispensed.
2. Carefully measure the time that it takes to dispense
exactly 2*** gal / 7.6 L of fuel.
3. If the time is greater than 11.8*** seconds there is
not a violation.
4. If the time is less than or equal to 11.8*** seconds,
repeat the test for another 2*** gal / 7.6 L into the
same vehicle (if possible). If the second test time
is also less than or equal to 11.8*** seconds, use a
calibrated fuel container to verify the accuracy of the
dispenser meter.
5. When the dispenser meter shows 5 gal / 18.9 L
and the volume dispensed is more than 6 cubic
inches over or under the 5 gal / 18.9 L mark on the
calibrated fuel container, note the amount in the
comment area of the fuels inspection form.
5a. If the volume in the calibrated fuel container
is 5 gal / 18.9 L or greater, record the two test
times and note as a violation.
5b. If the volume in the calibrated fuel container is
less than 5 gal / 18.9 L by more than 6 cubic
inches, conduct the test on another dispenser.
6. Dispose of the fuel following city, state, or federal
regulations.
Conventional Flo-Equalizer™
MODEL 4490
Recommended Installation, Maintenance and
Inspection Instructions
TROUBLESHOOTING GUIDE
Nozzle keeps shutting off or won't dispense... 1. Make sure dispenser is on and activated.
2. Check for blocked lter.
3. Reset the nozzle.
Low ow rate... 1. Check for blocked lter.
2. Remove Flo-Equalizer™ and recheck ow rate.
3. Verify dispenser is not in slow ow rate mode.
4. Check for leak detection failures.
Flow rate above 10 gpm / 37.9 Lpm... 1. Verify Flo-Equalizer™ is being used - either inside
or outside dispenser.
2. Check the Flo-Equalizer™ for debris.
• Inspect the entire dispensing system for damage.
• Check for leaks.
• Test nozzle for proper automatic shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
• Check for electrical conductivity.
Daily
• Check for leaks / stains.
Monthly
• Check nozzle auto shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
Annually
• Check for electrical conductivity.
• Check "remove after" date.
Gallons / Liters Minimum Time
2.0 gal / 7.6 L 11.8 seconds
3.0 gal / 11.4 L 17.7 seconds
4.0 gal / 15.1 L 23.6 seconds
5.0 gal / 18.9 L 29.5 seconds
***Any volume listed in the chart below may be used:
• All drive aways, maintenance and inspection activities
must be logged using the serial number of the
individual product.
• Apply city, state, or federal testing regulations as
appropriate.
ANY TEST / INSPECTION FAILURE REQUIRES
IMMEDIATE EQUIPMENT REPLACEMENT OR
REMOVAL FROM SERVICE.
MADE IN THE USA