Installation Guide
  1  HUSKYTOOLS.com
E109968- INSERT CUSTOMER WIRING INSTRUCTIONS
Please contact 1-888-43-HUSKY for further assistance.
230VAC Air Compressor Wiring Instructions
ELECTRICAL CONNECTIONS FOR 
PERMANENTLY CONNECTED ELECTRIC 
COMPRESSORS
NOTE:  If using 208 volts single phase, make sure the 
motor name plate states it is rated for 208 volts single 
phase. 230 volt single phase motors do not work on 208 
volts unless they have the 208 volt rating.
MOTOR LABEL
Ground Symbol
NOTICE: Electrical connections should only be performed by a 
qualified electrician.
INCOMING POWER
T1
L1
G
G
L2
T2
FUSED DISCONNECT
OR CIRCUIT BREAKER
PRESSURE
SWITCH
MOTOR
230VAC SINGLE PHASE WIRING
 C602H  3.7HP  17.2  10 - Gauge  6ft.
C801H/C803H   5HP   22   8 - Gauge  6ft.
 Model  HP  AMPS  230V  Allowable
Max Length
Single Phase
Wire Size Chart
GENERAL. The motor rating, as shown on the motor 
nameplate, and power supply must have compatible 
voltage, phase and hertz characteristics.
WIRE SIZE.  The electrical wiring between the power 
supply and electric motor varies according to motor 
horsepower and other factors. Install adequately sized 
power leads to protect against excessive voltage drop 
during start-up. Refer to the applicable electric codes in 
your area for information on selecting the proper wire 
size and securing electrical connections. If you connect 
additional electrical equipment to the same circuit, 
consider the total electrical load when selecting the 
proper wire size. DO NOT USE UNDERSIZE WIRE.
MINIMUM WIRE SIZE. (USE 75 DEGREE C COPPER WIRE) 
Make sure voltage is correct with the motor wiring. Refer 
to the motor label for the running HP rating. This will 
determine the size wire needed. See example below. 
Recommended wire sizes may be larger than the 
minimum set up by the local ordinances. If so, the larger 
wire size should be used to prevent excessive line 
voltage drop. The additional wire cost is very small 
compared with the cost of repairing or replacing a motor 
electrically “starved” by the use of supply wires which 
are too small. Also, if a lead wire longer than 6 ft. is 
Compressors equipped with motor starters include a 
ground terminal inside the starter enclosure. For 
compressors with single-phase motors having thermal 
overload protection and no motor starter, the ground 
terminal is located inside the pressure switch. Ground 
must be established with a grounding wire size according 
to the voltage and minimum branch circuit requirements 
printed on the compressor specifications decal. Ensure 
good bare metal contact at all grounding connection 
points, and ensure all connections are clean and tight. 
WARNING: Electrical installation and 
service must be performed by a 
qualified electrician who is familiar with 
all applicable electrical codes. 
WARNING: Improper grounding can 
result in electrical shock and can cause 
severe injury or death.This product must 
be connected to a grounded, metallic, 
permanent wiring system or an 
equipment-grounding terminal or lead. 
All grounding must be performed by a 
qualified electrician and comply with 
applicable electric codes.
needed, consult a local electrician for alternative wiring 
options.
FUSES.  Refer to applicable local codes to determine the 
proper fuse or circuit breaker rating required. When 
selecting fuses, remember the momentary starting current 
of an electric motor is greater than its full load current. 
Time delay or “slow-blow” fuses are recommended.
GROUNDING.  In the event of an electrical short circuit, 
grounding reduces the risk of electric shock by providing 
an escape wire for the electric current. Ground terminals 
are identified with a ground symboland/or the letters “G”, 
“GR” or “PE” (Potential Earth). 