Owner's Manual

INSTALLATION INSTRUCTIONS
1. Turn off dispenser and relieve line pressure.
2. Use pipe thread sealant (not Teon tape) approved for gasoline on the male threads of
hose section.
3. Tighten approximately 1 or 2 turns past hand tight - do not overtighten.
4. Pressurize system and visually check for leaks.
5. Test nozzle for proper automatic shut off between 5 - 10 gpm / 18.9 - 37.9 Lpm.
DO NOT OVERTIGHTEN. USE WRENCH ON HOSE NUT ONLY.
TESTING / MAINTENANCE / INSPECTION
Conventional Nozzles
X & 1A
Nozzles
Recommended Installation, Maintenance
and Inspection Instructions
WARNING Designed for use at motor fuel dispensing facilities only.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 1 009024-11 12/2011
IF DRIVE OFF OCCURS
Daily
• Check for leaks / stains.
• Check for loose spouts.
• Check for damage.
• Check for bent lever.
Check for broken clip / trigger
spring.
Monthly
Check nozzle automatic shut off
between 5 - 10 gpm / 18.9 -
37.9 Lpm.
• Check "remove after" date.
Annually
Check for electrical conductivity.
• Lubricate main valve stem.
All drive aways, maintenance and
inspection activities must be logged
using the serial number of the individual
product.
Apply city, state, or federal testing
regulations as appropriate.
ANY TEST / INSPECTION FAILURE
REQUIRES IMMEDIATE EQUIPMENT
REPLACEMENT OR REMOVAL FROM
SERVICE.
MADE IN THE USA
Model #
074703
074704
074707
074708
074759
074761
074763
074764
074772
074773
159403
159404
159407
159408
159423
159424
159453
159454
159457
159458
159463
159464
159467
159468
209803
209804
209807
209808
209859
209861
209863
209864
209872
209873
265703
265704
265707
265708
265724
265744
265745
265753
265754
265757
265758
265763
265764
498403
498404
498407
498408
498461
498462
498466
498467
503703
503704
538403
538404
538476
696103
696104
696107
696108
696159
696161
696163
696164
696172
696173
696403
696404
696407
696408
696459
696461
696463
696464
696472
696473
Turn off dispenser and relieve line pressure.
• Visually check for fractured spout shear groove.
• Check for leaks.
• Check spout tip - should be in round and sensing port should be clear of debris.
• Perform ow test of nozzle automatic shut off between 5 - 10 gpm / 18.9 - 37.9 Lpm.
• Check for electrical conductivity.