CONFIG MENU (continued)
3- DESCRIPTION
Press 3 on the Keypad to enter the Description
Submenu.
This screen provides for a 16 character description
of the Protocol unit for user identification on
Hussnet™.
Press the CLR key.
Key in the description . Press Shift Upper to use
the red (upper) letters and Shift Lower to use the
blue (lower) letters.
Press ENT.
Press ESC to return to PROTOCOL SETUP MENU.
Press ESC again to return to CONFIG MENU.
4- ALARM OUTPUT
Press 4 on the Keypad to enter the Alarm Output
Submenu.
The alarm output feature allows one of the 24
available outputs to be energized during the
occurance of any alarm (High/Low Pressure,
High/Low Temp, etc.)
The output number refers to a relay which is wired
into the main Protocol Alarm Relay (AR).
Key in the number (between 1 and 24). Make sure
that the output is available and not being used by
another function (defrost, lighting or temperature
control).
Press ENT.
Press ESC to return to PROTOCOL SETUP MENU.
Press ESC again to return to CONFIG MENU.