IGSS-FMSS-L-0708 General Instructions Table of Contents This Booklet Contains Information on: FMSS-L, FMSS-L-L-Remote The FMSS-L, FMSS-L-L is a single-deck, refrigerated, self-service merchandiser, which offers additional related display when positioned in front of a “Parent” service case. The FMSS-L, FMSS-L-L only fits under Hussmann Chino Style cases. Shipping Damage All equipment should be thoroughly examined for shipping damage before and during unloading.
Rev. 0708 Cut and Plan Views Drain 9 7/8" 16" (21 1/2" S.C.) Ref. Drop In Elec. 2 5/8" 4' (VARIABLE LENGTHS) 16'' Remote 21 1/2" S.C. *Dimensions adjust at theses points to match service case height 24" 4 1/2" 3 1/2" 12 1/2" n *10 1/2" *26 3/8" Fa 26'' Remote 28 5/8" S.C. 11 3/4" 6 1/8" 13 1/2" 3 7/8" Remote 8 7/8" S.C.
IGSS-FMSS-L-0708 Installation (Cont'd) NOTE: 6. Slide second case up to first case snugly. Then level second case to the first case so glass front, bumper and top are flush. A. To avoid removing concrete flooring, begin lineup leveling from the highest point of the store floor. B. When wedges are involved in a lineup, set them first. All cases were leveled and joined prior to shipment to insure the closest possible fit when cases are joined in the field.
Rev. 0708 Installation (Cont'd) Bumper Installation Instructions Step 2: Use silicone lubricant to help the bumper slide into the channel. Step 1: Make sure the aluminum channel and end caps are installed. Step 3: Starting on one end: while inserting the bumper, push it up against the end cap to prevent the bumper from shrinking after installation (when it gets cold).
IGSS-FMSS-L-0708 Installation (Cont'd) Boston Series 2000 NOTE: Flexible top: Over cut vinyl 1/8" for every 4' section for the flexible top to ensure a proper fit. NOTE: Rigid Top: Do not over cut. 1. Attach the base and end/corner cap to the desired surface by inserting #8 pan head screws through the pre-slotted holes in both the end cap and the base. Insert screws through the two holes of end cap and tighten. 2a. Flexible Top: Butt end of the vinyl top against end/corner cap.
Rev. 0708 Installation (Cont'd) Boston 2000 Eco Series 1. Attach the base and end/corner cap to the desired surface by inserting #8 pan head screws through the pre-slotted holes in both the end cap and the base. Insert screws through the two holes of end cap and tighten. 2a. Flexible Top: Butt end of the vinyl top against end/corner cap. While applying pressure, bend back vinyl top so that vinyl legs are positioned within the base grooves.
IGSS-FMSS-L-0708 Installation (Cont'd) Boston 1000 Series NOTE: Flexible top: Over cut vinyl 1/8" for every 4' section for the flexible top to ensure a proper fit. NOTE: Rigid Top: Do not over cut. Installation 1. Attach the base and end/corner cap to the desired surface by inserting #8 pan head screws through the pre-slotted holes in both the end cap and the base. Insert screws through the two holes of end cap and tighten. 2a. Flexible Top: Butt end of the vinyl top against end/corner cap.
Rev. 0708 Plumbing Waste Outlet and P-TRAP The waste outlet is located at the left hand end of these fixtures allowing drip piping to be run under the fixture lengthwise. A 1” P-TRAP and threaded adapter are supplied with each fixture. The P-TRAP must be installed to prevent air leakage and insect entrance into the fixture.
IGSS-FMSS-L-0708 Refrigeration (Cont'd) Thermostatic Expansion Valve Location This device is located on the same side as the refrigeration stub. An Alco balanced port expansion valve model is furnished as standard equipment, unless otherwise specified by customer. Expansion Valve Adjustment Expansion valves must be adjusted to fully feed the evaporator.
Rev. 0708 Electrical Wiring Color Code BEFORE SERVICING ALWAYS DISCONNECT ELECTRICAL POWER AT THE MAIN DISCONNECT WHEN SERVICING OR REPLACING ANY ELECTRICAL COMPONENT. This includes (but not limited to) Fans, Heaters Thermostats, and Lights. Field Wiring and Serial Plate Amperage Field Wiring must be sized for component amperes printed on the serial plate. Actual ampere draw may be less than specified.
IGSS-FMSS-L-0708 User Information (Cont'd) 8. Avoid the use of supplemental flood or spot lighting. Display light intensity has been designed for maximum visibility and product life at the factory. The use of higher output fluorescent lamps (H.O. and V.H.O.), will shorten the shelf life of the product. Important Steps 1. Do not set temperature too cold, as this causes product dehydration. Product Temperature: 10°F!. Set thermostat to cut in at -5°F discharge air. 2.
Rev. 0708 Maintenance FOR PROMPT SERVICE When contacting the factory, be sure to have the Case Model and Serial Number handy. This information is on a plate located on the case itself. BEFORE SERVICING ALWAYS DISCONNECT ELECTRICAL POWER AT THE MAIN DISCONNECT WHEN SERVICING OR REPLACING ANY ELECTRICAL COMPONENT. This includes (but not limited to) Fans, Heaters Thermostats, and Lights.
IGSS-FMSS-L-0708 3. Use Alkaline, Alkaline Chlorinated or Non-chloride Containing Cleaners While many traditional cleaners are loaded with chlorides, the industry is providing an ever increasing choice of non-chloride cleaners. If you are not sure of your cleaner’s chloride content contact your cleaner supplier. If they tell you that your present cleaner contains chlorides, ask for an alternative.
Hussmann Corporation, Int'l. 13770 Ramona Avenue Chino, CA. 91710 (909)-590-4910 Lic.#: 644406 A BALLAST 125-01-3266 FULHAM LH3-120-L CAP UNUSED RED LEAD 9/5/07 DATE: BLK # 14 D Defrost 120 V KLIXON™ THERMODISK 20420L15-913-302 L20-1.5 00003382 TO DEFROST CONTROL PANEL C Refrig 120 V RELAY MARS 90341 COIL:~115V PN:125-01-1343 2 1 RED # 14 3' CASE - ELECTRIC DEFROST FMSS-L/M CASES DRAWING #: RELAY OMRON G7L-2A-TUBJ-CB-AC24D 125-01-3182A DEFROST HEATERS (18") (2) 660W 2.
1 2 3 DATE: D Defrost ON 115 V KLIXON™ THERMODISK 20420L15-913-302 L20-1.5 00003382 2 RELAY OMRON G7L-2A-TUBJ-CB-AC24D 125-01-3182A FMSS-L/M CASES DRAWING #: PAGE 1 OF 1 W1400009 POWER: ~208/240 VAC - 1Ø - 50/60Hz. - 4W NOTE: CASE MUST BE GROUNDED L1 L2 ~208/~240VAC - 1Ø - 50/60Hz. RELAY MARS 90341 COIL:~115V PN:125-01-1343 8' CASE - ELECTRIC DEFROST-DUAL TEMP DRAWN BY: D.
CAP OFF WIRE CAP OFF WIRE BALLAST 125-01-3265 FULHAM LH2-120-L Hussmann Corporation, Int'l. 13770 Ramona Avenue Chino, CA. 91710 (909)-590-4910 Lic.#: 644406 1 2 3 GNL ~ 115VAC 50/60Hz. 2 1 C Case ON 115 V DATE: D Defrost ON 115 V L1 L2 ~208/~240VAC - 1Ø - 50/60Hz. FMSS-L/M CASES DRAWING #: PAGE 1 OF 1 W1400015 POWER: ~208/240 VAC - 1Ø - 50/60Hz.
BALLAST 125-01-3267 FULHAM LH4-120-L CAP OFF WIRE Hussmann Corporation, Int'l. 13770 Ramona Avenue Chino, CA. 91710 (909)-590-4910 Lic.#: 644406 1 2 3 2 1 C Case ON 115 V D Defrost ON 115 V DATE: L1 L2 ~208/~240VAC - 1Ø - 50/60Hz. RELAY MARS 90341 COIL:~115V PN:125-01-1343 FMSS-L/M CASES DRAWING #: PAGE 1 OF 1 W1400012 POWER: ~208/240 VAC - 1Ø - 50/60Hz.
F21T5-36" 125-03-1129 F21T5-36" 125-03-1129 F21T5-36" 125-03-1129 BALLAST 125-01-3266 FULHAM LH3-120-L Hussmann Corporation, Int'l. 13770 Ramona Avenue Chino, CA. 91710 (909)-590-4910 Lic.#: 644406 1 2 3 GNL ~ 115VAC 50/60Hz. 2 1 C Case ON 115 V DATE: D Defrost ON 115 V L1 L2 ~208/~240VAC - 1Ø - 50/60Hz. FMSS-L/M CASES DRAWING #: PAGE 1 OF 1 W1400016 POWER: ~208/240 VAC - 1Ø - 50/60Hz.
Hussmann Corporation, Int'l. 13770 Ramona Avenue Chino, CA. 91710 (909)-590-4910 Lic.#: 644406 CANOPY LIGHTING (2) FP28T5/830 125-03-1131 SOLENOID VALVE 225-01-3206 REVISIONS: #: DESCRIPTION: LOADING 208 V 240 V L1 11.4 12.9 11.1 L2 9.
HUSSMANN® CORPORATION 13770 RAMONA AVENUE CHINO, CA.91710 (909) 590-4910 LIC.#: 644406 DATE: RELAY MARS 90249Q 225-01-2045 LOW TEMP. T-STAT MEDIUM TEMP.
IGSS-FMSS-L-0708 Appendices 1.3 A clogged waste outlet blocks refrigeration. The installer is responsible for the proper installation of the system which dispenses condensate waste through an air gap into the building indirect waste system. 1.
Rev. 0708 Appendices (Cont'd) 7. Are there unusual draft conditions (from heating/air-conditioning ducts, open doors, etc.)? 8. Is there exposure to direct sunlight? 9. Are display signs blocking or diverting airflow? 10. Are the coils of the refrigerator iced up? 11. Is the store ambient over 75°F, 55% RH as set forth in ASHRAE Standard 72 and ASHRAE Standard 117? 12. Are the shelf positions, number, and size other than recommended by Hussmann? 13. Is there an improper application or control system? 14.
IGSS-FMSS-L-0708 Appendices (Cont'd) d) Care must be taken when cross merchandising products to ensure that potentially hazardous vegetable products are not placed in non refrigerated areas. e) Display and storage equipment doors should be kept closed during periods of inactivity. f) Minimize the transfer time of perishables from storage to display. g) Keep meat under refrigeration in meat cutting and processing area except for the few moments it is being handled in processing.
IGSS-FMSS-L-0708 Service Record Last service date: By: _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________