Operating and Installation Instructions MODEL: GSVM – Self Contained Medium Temperature Cases for Dairy, Beverages, and Deli Products OII - GSVM January 2005
TABLE OF CONTENTS Page Introduction Inspection 4 4 Location and Clearance Skid Leveling Sealing 4 4 5 5 Access Panel Removal Legs Serial Plate Air distribution and Product Loading Power Requirements Electrical Box Power Switch Defrost Time Clock Connections Drains 5 5 5 6 6 6 6 6&7 7 7 & 10 Dimensions Electrical BTU Capacity Shelving Maximum Weight Capacities 8 8 8 8&9 Temperature Control Condensing Unit Shelves Thermometer Lighting Light Switches Ballasts Cleaning Exterior, Interior, Stainless Stee
TABLE OF CONTENTS CON’T Page Refrigeration Leak Testing Evacuation Temperature Control Evaporator Fan Motors 11 12 12 13 13 Trouble Shooting Charts 14 – 16 GSVM Accessories 16 – 17 Warranty and Parts Information 17 Wiring Diagrams 18 – 21 This GSVM case was manufactured in Gloversville, New York. Our phone #’s are (518) 725-0644 for New York State residents and our toll free #800-753-7790 for outside New York – should you have further questions.
INTRODUCTION – Save all packaging materials and move the cabinet as little as possible prior to inspection. The Hussmann Model GSVM open vertical merchandiser offers versatility in the display of medium temperature (3541ºF) products such as diary products, prepared salads, pizza and fresh entrees that are pre-chilled in a cooler.
The procedure is repeated on the op- DRAINS – posite end. When the leg levelers are in place, the case may be slid off the skid and Remote draining is not required in placed in its final location. self-contained models.
AIR DISTRIBUTION and PRODUCT LOADING – ELECTRICAL BOX – The electrical box is located behind the louvered access panel. The box is capable of sliding out for service after the hold down screw is removed. This cabinet has a forced-air circulation system. Air flows through the back wall over the product on the shelves, as well as out the honeycomb diffuser located above the product, across the face of the product (air curtain) and into the return air grill.
each. There are 4 defrost on the 5272 (2 a.m., 8 a.m., 2 p.m., and 8 p.m.) at 30 minutes each Additional defrost may be required for cases located in high humidity or high us age cases. If possible, avoid setting a defrost during the day, or peak usage periods. THE CLOCK TIME POINTER SHOULD BE SET TO THE CORRECT TIME OF DAY WHEN THE CABINET IS READY TO BE STARTED. b. Inspect the refrigeration lines for any visible damage or chafing. c. Replace electrical box cover. d. Replace the louvered access panel. e.
SPECIFICATIONS – DIMENSIONS Model Length GSVM-4060 40" GSVM-4072 40" GSVM-5272 52" ELECTRICAL MODEL NO. Volts/Hz/Phase GSVM4060 GSVM4072 GSVM5272 GSVM5272 115/60/1 115/60/1 115/60/1 115/60/1 Exterior Width 30 5/8" 30 5/8" 30 5/8" REFRIGERANT TYPE R-134a R-134a R-134a R-404A Height 60" 72" 72" RUN FUSE AMPS AMPS 15 20 17 25 20 25 17.25 25 POWER CORD YES NO NO NO ** ** The GSVM-5272 changed to R404A in January 2000. Check the Serial Plate to verify the correct refrigerant.
Bottom Sheet Metal Area Stand. 13”/15” shelves Stand. 13”/15” shelves w/optional upslope 6º adapters Optional Wire Baskets OPERATION and MAINTENANCE It is important that the two previous sections of this installation booklet have been read and followed carefully before attempting to start up the equipment. A thorough inspection should be made prior to start up to assure that there are no loose nuts, bolts, electrical connections or refrigeration lines rubbing or chafing.
correspond to the actual cabinet temperature due to the bulb location and depending on various conditions, a certain amount of time lag will be noticed between the new setting and the resulting temperature. CONDENSING UNIT – A regular program should be set up for cleaning the fin-and -tube condenser. Normally, this cleaning is required every 3 to 4 months, but the individual store application may shorten or lengthen this time period. Dust and dirt accumulation can cause serious efficiency loss.
LIGHTING – Interior lighting is provided by a cool white fluorescent bulb under the top header (standard), and additional lights under each shelf. The tubes are sleeved to maintain proper heat around the bulb for maximum light intensity and to protect the product in case of breakage. The tubes can be replaced without removing shelves or product. To replace the bulb, twist th e bulb and slide the prongs clear of the lampholder.
CLEANING STAINLESS STEEL SURFACES – Generally soap and water will be sufficient for most cleanings when done often and regularly. When necessary, several cleaning agents can be used. Some of themare Comet, Bab-O, Liquid NuSteel, Cooper’s Stainless Steel Cleaner, and Allen’s Stainless Steel Cleaner. REFRIGERATION – The GSVM models employ a refrigeration system using a hermetic compres sor. The GSVM4060 and GSVM4072 sys tems employ a capillary tube for refrigerant flow control.
Be sure that all s ervice valves are open to allow all of the mixture to be discharged. b. Connect a deep-drain vacuum pump to both the high and l ow side of the system. Pull a vacuum on the system to at least 1500 microns. into the system through a new drier in the charging manifold line. A 16 cubic inch drier is sufficient for this purpose. d. Repeat steps 2 and 3 two more times, the third time evacuating the system to 500 microns. c.
TROUBLE SHOOTING CHARTS TROUBLE PROBABLE CAUSE Compressor will not start no 1. Power disconnected noise Compressor will not start, cuts out on overload SOLUTION 1. Check service cord or wiring connection. 2. Blown fuse or breaker 2. Replace fuse or reset breaker 3. Defective or broken wiring 3. Repair or replace 4. Defective overload 4. Replace 5. Defective temperature control 5. Replace 1. Low voltage 1. Check voltage at cabinet, should not be more than 5% below rating. 2.
4. Refrigerant overcharge 4. Purge system, evacuate and recharge. 5. Low voltage, compressor 5. Check voltage at cycling on overload compressor should not be more than 5% below rating Compressor runs continuously. Product too warm Compressor runs continuously. Product too cold 1. Short of refrigerant 1. Leak check, replace drier, evacuate and recharge 2. Inefficient compressor 2. Replace 1. Defective control 1. Replace 2. Control sensing element not in positive contact 2.
Ballast Hums 1. Check voltage 2. Replace ballast GSVM ACCESSORIES The following is a description of the various accessories available for the GSVM, including sketches, where applicable of the many shelving/wire goods items available. CASTER KIT – Consists of 5" braking casters, which screw in to the standard threaded holes in the four corners under the case occupied by the standard leg levelers, which will have to be removed. The kit will add 5 5/8" to the height of the case.
SHELF UPSLOPE ADAPTER KIT – This kit consists of (4) zinc coated wire adapters to increase the two standard shelves’ upslope from 1 1/2º to 6º. PRICE TAG MOLDING KIT – This kit consists of aluminum price tag molding for the standard shelves. This molding will hold both 1" and 1.235" standard price tags. (Note that the standard shelves accept 1.235” tags). WIRE PRODUCT STOP KIT – This kit consists of a 2” high chrome plated open wire stops for the standard shelf.
WARRANTY PARTS PROCEDURE Same as first three items in Ordering Replacement Parts Procedure. Give original installation date of cabinet and, if possible, forward a copy of the original invoice or delivery receipt. All shipments of in-warranty replacement parts will be invoiced from the factory until such time as the defective part is returned and proved to be defective by our Quality Control Department. Contact your Hussmann Distributor for instructions on returning in-warranty parts.
UPPER LIGHT LAMP RED WIRE HARNESS RED BLK EVAP. FANS LIGHT SWITCH BLK S OPTIONAL SHELF LIGHT COMPRESSOR RED PROTECTOR BLK C 2 1 LAMP #1 RELAY TEMP. CONTROL COND. FAN TIME CLOCK T RED BALLAST LIGHT SWITCH STARTER BLK S WHT BLK 2 N BLU 4 GRN STD. SHELF LIGHT 26 25 ELEC-TRON WHT 12 24 23 10 8 9 6 7 WHT 11 4 WHT 5 WHT 2 LIGHT SWITCH BLK 3 BALLAST 1 BLK BALLAST LAMP X BLU 3-S-226 S 1 3 WHT BLK BLK WHT S STD.
UPPER LIGHT LAMP RED WIRE HARNESS RED BLK S OPTIONAL SHELF LIGHT EVAP. FANS LIGHT SWITCH BLK LAMP COMPRESSOR BALLAST RED PROTECTOR BLK LIGHT SWITCH C 2 1 BLK #1 RELAY TEMP. CONTROL WHT COND. FAN TIME CLOCK T RED STD. SHELF LIGHT S STARTER S 2 BLK LAMP N 1 BLU 4 GRN 3 X BLU WHT WHT BALLAST BLK LIGHT SWITCH LAMP 26 25 ELEC-TRON 12 24 23 10 8 7 9 6 5 11 2 WHT 4 STD.
UPPER LIGHT LAMP RED WIRE HARNESS RED EVAP. FANS BLK S OPTIONAL SHELF LIGHT LIGHT SWITCH BLK LAMP COND. FANS BLU RED WHT PROTECTOR BLK BALLAST C 2 1 #1 RELAY TEMP. CONTROL LIGHT SWITCH BLK COMPRESSOR TIME CLOCK WHT RED T STD. SHELF LIGHT S LAMP STARTER S BLK 1 N 2 BLU 4 GRN 3 X BLU WHT BALLAST WHT WHT BLU BLK LIGHT SWITCH LAMP 26 25 WHT BLK BLK WHT GRD WHT BALLAST CONDENSATE PAN LIGHT SWITCH BLK BLK WHT STD.
UPPER LIGHT LAMP RED WIRE HARNESS RED BLK S OPTIONAL SHELF LIGHT EVAP. FANS LIGHT SWITCH BLK LAMP COND. FANS COMPRESSOR BALLAST RED R BLK LIGHT SWITCH C BLK TEMP. CONTROL 1 WHT TIME CLOCK T S RED STD. SHELF LIGHT STARTER S 2 BLK LAMP N 1 BLU 4 GRN 3 X BLU WHT WHT BALLAST BLK LIGHT SWITCH LAMP 26 25 ELEC-TRON 12 24 23 10 8 7 9 6 5 11 2 WHT 4 STD. SHELF LIGHT 1 S 3 WHT 3-S-226 BALLAST BLK WHT BLK BLK WHT BALLAST LIGHT SWITCH BLK WHT BLK S STD.