InstallatIon guIde
Legislation
The installation of your HWAM stove must always comply with all national and local building regulations.
It is always a good idea to consult a chimney sweeper before you install the stove.
Requirements on the room
It must always be possible to obtain a supply of fresh air for the combustion to the room where the
stove is to be installed. A window that can be opened or an adjustable ventilator is considered suf-
ficient, but it is also possible to connect a HWAM fresh-air system to the stove. The air inlet/grating
must be placed so that they do not become blocked.
Fresh air system (optional extra)
The HWAM 3310 and HWAM 3320 can be equipped with an optional fresh air system.If you wish to
install a fresh air system on your stove, you have the following options:
1) Stove mounted on the wall: Connect the fresh air system on the lower back of the stove.
2) Stove mounted on a plinth: Connect the fresh air system either on the lower back of the stove or
on the back of the plinth.
Please ensure that the hole (D4) is covered by the sealing plate accompanying the fresh air con-
nection kit.
Load bearing surface
Before installing the stove, make sure that the surface it will stand on can carry the weight of the
stove and the chimney. The weight of the chimney must be calculated based on its dimensions and
height. The stove’s weight:
HWAM 3310 without plinth: 92 kg with plinth: 107 kg
HWAM 3320 without plinth: 95 kg with plinth: 110 kg
Distance to inflammable material, drawing A
Your HWAM stove must always be installed on a fire-proof surface. If installed on a wooden floor or
similar surface, the floor must be covered by a fire-proof material.
Note: HWAM 3310 and HWAM 3320 must always be mounted on the wall or on a plinth.
Min. distances:
1. To brick wall at the rear 10 cm*
1. To inflammable wall at the rear 15 cm
2. To brick wall at the side 10 cm
2. To inflammable wall at the side 25 cm
3. To brick wall at the side, corner installation 10 cm
3. To inflammable wall at the side, corner installation 15 cm
4. Distance to furniture in front 80 cm
For wall-mounting, the stove must be placed at least 24 cm above any inflammable flooring. This also
applies to any floorboard placed on the floor.
Please be aware that not all glass parts are heat-resistant. For this reason, a glass wall should sometimes
be treated as a flammable wall, in which case we ask you to contact your local chimney sweep or glass
producer to hear at what distance the stove should be kept from glass.