Installation Instructions
Installation Manual
Page
28
When servicing or replacing parts within the micro-boiler, label all wires prior
to disconnection to facilitate an easy and error-free reconnection. Wiring
errors can cause improper and dangerous operation. Verify proper operation
after servicing.
Follow the electrical code requirements of the local authority having
jurisdiction. In the absence of such requirements, follow the latest edition of
the National Electrical Code ANSI/NFPA 70 in the U.S. or the latest edition of
CSA C22.1 Canadian Electrical Code Part 1 in Canada.
-ELECTRICAL CONNECTIONS-
• The condensate drain is at atmospheric pressure (non-pressurized) and
therefore must be allowed to drain freely with gravity only. Please ensure
that there are no blockages along the condensate drain tube. All portions
of the condensate drain (neutralizer and drain tube) must be at a lower
elevation than the micro-boiler to prevent condensate water from building
up inside the heat exchanger.
• Condensate cannot be effectively neutralized if the neutralizer elements
inside the Neutralizer accessory have been completely consumed. If this
happens condensate will remain acidic and can possibly cause damage
to items such as pipes, concrete, etc., if drained improperly.
• The Neutralizer cartridge is designed to last for 3 years before
replacement. However, the actual life of the neutralizer may vary,
depending on the application and usage. Please ensure that the
cartridge is properly replaced before the neutralizer elements have been
completely consumed.
• All preventive measures and safety practices must be adhered to when
draining condensate. The manufacturer will not be responsible for any
damage caused by condensate.
• A drain pan, or other means of protection against water damage, is
required to be installed under the micro-boiler in case of leaks.
All micro-boilers come with a power plug instead of a junction box.
Installation
CAUTION
WARNING
WARNING