APPLICATIONS
-Space heating applications-
In order to purge air in water pipes within a closed-loop system, an
air vent, air separator, and expansion tank should be installed in
the system. The system must follow primary/secondary plumbing
design specication. (Optional Hydro Smart pre-built space heating
panels incorporate all these features and are located in the optional
accessories section starting on p. 34.
Water temperature over 125° F (52° C) can cause severe burns
instantly or death from scalding.
Chemicals such as diluted Glycol can be used for radiant oor heating
only. The diluted solution of glycol must contain between 25 and 50 %
of Glycol. Be aware that in closed-loop glycol systems, low pressure
in the heat exchanger can cause low-temperature boiling, resulting
in excessive noise and damage to the micro-boiler. Consult with the
glycol maker for specications prior to use.
The micro-boiler manufacturer requires primary/ secondary plumbing
congurations for space heating applications. See description below.
WARNING
The Hydro Smart panel systems operate on a principal of hydraulic separation between the boiler
circuit and the emitter circuit (tubing, baseboard, ect.). This hydraulic separation creates the ability to
adjust the ow in the boiler circuit independently from the emitter circuit while still passing heat from
the boiler to the emitters. Flow rate from boilers need to be adjusted to manufacturer's specications.
Flow rate for emitters need be adjusted for heat output performance.
For more information on hydraulic separation visit this website:
www.calef.com/sites/default/les/le/hydraulicseparation-tr07.pdf
-Hydraulic Separation-