Troubleshooting
TROUBLESHOOTING
-General-
PROBLEM SOLUTIONS
TEMPERATURE and AMOUNT OF HOT WATER
The water is not hot enough.
Compare the ow and temperature. See the chart on p. 58.
Is the plumbing correct(primary/secondary, pump size, ect.)?
Is the gas supply valve fully open? (p. 33)
Is the gas line sized properly? (p. 24)
Is the gas supply pressure sufcient? (p. 20 and p. 25)
Is the set temperature set too low? (p. 43 to p. 45)
The water is too hot. Is the set temperature set too high? (p. 43 to p. 45)
The hot water is not available
when there is a call for heat.
Make sure the unit has 120VAC, 60Hz power supply.
Is the temperature controller power button turned on?
Is the gas supply valve fully open? (p. 33)
Is the Y-strainer clean?
Can the emitters sufciently draw at least 0.5GPM (1.9 L/min)
through the micro-boiler. (p. 43)
Is the unit frozen? (p. 46)
Is there enough gas in the tank/cylinder? (For Propane)
Is it plumbed backwards with reverse plumbing?
The hot water turns cold and
stays cold.
Is the ow rate enough to keep the unit running? (p. 43)
Is the gas supply valve fully open? (p. 33)
Is the Y-strainer clean?
Is the system clean of debris and obstructions?
Fluctuation in hot water
temperature.
Is the gas line sized properly? (p. 24)
Is the supply gas pressure sufcient? (p. 20 and p. 25)
Is the plumbing correct?
WATER HEATER
Unit does not ignite when
water goes through the unit.
Is the power on the micro-boiler?
Is the gas on?
Is the ow rate over 0.5GPM (1.9 L/min)? (p. 43)
Is the system Y-strainer clean?
Check for reverse connection and cross connection. (p. 30)
Is the temperature controller power button on?(p. 43 & p. 44)
Check if the system return temperature is to high?
The fan motor is still spinning
after operation has stopped.
This is normal. After operation has stopped, the fan motor keeps
running from 15 to 70 seconds in order to re-ignite quickly, as well
as purge all the exhaust gas out of the ue.
Abnormal sounds from the
micro-boiler.
Is the correct gas type of micro-boiler installed? (LP or NG)
Are the DIPswitch settings for your altitude set correctly?(p. 29)
Check the ame quality. (p. 47)
Is the intake or exhaust vent blocked? (p. 10)
Is the vent length and diameter correct? (p. 11 to p. 16)
Is the manifold pressure set correctly? (p. 4)
Unit sounds abnormal while in
operation
Contact the manufacturer at 1-763-331-3066
REMOTE
CONTROLLER
Controller does not display
anything when the power
button is turned on.
Make sure the micro-boiler is supplied with power.
Make sure the connection to the micro-boiler is correct.
Note: When the micro-boiler has not operated for ve minutes or
more, the display of the controller turns off to conserve energy.
An ERROR code is displayed. Please see "-ERROR CODES-" on page 49.