Installation Instructions

24
Pressure relief valve
The micro boiler has a high-temperature shutoff switch built in as a standard safety feature (called a
Hi-Limit switch) therefore a “pressure only” relief valve is required.
This unit does not come with an approved pressure relief valve.
An approved pressure relief valve must be installed on the hot water outlet.
The pressure relieve vale must conform to ANSI Z21.22 or Can 1-4.4 and installation must follow
local codes.
The discharge capacity must be at least 199,000 BTU/h.
The pressure relief valve needs to be rated for a maximum of 150 psi (1 MPa).
The discharge piping for the pressure relief valve must be directed so that the hot water cannot
splash on anyone or on nearby equipment.
Attach the discharge tube to the pressure relief valve and run the end of the tube to within 6
in.(152 mm) from the oor. This discharge tube must allow free and complete drainage without any
restrictions.
If the pressure relive valve installed on the micro boiler discharges periodically, this may be due to
a defective thermal expansion tank or defective pressure relief valve.
The pressure relief valve must be manually operated periodically to check for correct operation.
No valve must be placed between the relief valve and the micro boiler.
CONDENSATE DRAIN
The micro boiler does not include a built-in condensate neutralizer cartridge for reducing the pH
level of condensate water. If local codes dictate that condensate must be neutralized prior to
drainage, a condensate neutralizer must be installed. An accessory Neutralizer assembly is sold
separately.
In the absence of applicable local codes and regulations, th manufacture recommends that con-
densate be disposed of into a standard drain. Connect a drain tube from the condensate drain port
(shown below) located on the bottom of the micro boiler to a standard drain.
Follow all code requirements
of the local authority on
condensate neutralizers and
whether or not they are required
for the installa
Condensate drain port