Fault Analysis of Error Codes
If the error code is displayed on the computer board of the micro boiler or remote controller and/or
temperature controller, please check the following. After checking, Consult with the manufacturer.
Remote
Green
LED
Diagnosis
descrip
031
One Time Incorrect DIPswitch
se
101
Five Times
Check the DIPswitch se
on the PCB (Part #701).
Warning for the
“991” error code
111
Three Times failure
Check the gas type of the micro-boiler.
Check if there is any blockage in the intake air and/
or exhaust.
If the micro-boiler is installed as a direct-vent
system, check whether there is enough distance
between the intake air terminal and the exhaust
terminal.
Check the
/eleva of area of where the
micro-boiler is installed.
Check if there is grease and/or dirt in the burner (Part
#101) and the fan motor (Part #103), especially if the
micro-boiler has been installed in a contaminated area.
121
Three Times Loss of flame
311
Two Times Heat exchanger
thermistor failure
321
Two Times
331
Inlet thermistor
failure
Two Times
341
Outlet thermistor
failure
Check for connec
reakage of wires and/or
debris on thermistor (Part #407, 408, 411, 715).
Two Times
Check if the Hi-limit switch (Part #412) is properly
Check for connec reakage of wires (Part #413, 708,
709, 710, 712), burn marks on the computer board (Part
#701), and/or soot on the ame rod (Part #108).
Check if there is a buzzing spark
sound
coming from the burner (Part #101) when
micro-boiler prepares for combus
Listen for the double “clunk” sound coming from gas
valve assembly (Part #102) when micro-boiler goes
into combus
Check if there is leaking from heat exchanger (Part #401).
Check if the Hi-limit switch (Part #412) is properly
Check for c reakage of wires (Part #413,
708, 709, 710, 712), burn marks on the computer
board (Part #701), and/or soot on the flame rod
(Part #108).
Check if there is leaking from heat exchanger (Part #401).
Exhaust thermistor
failure