Installation Instructions

26
The condensate drain is at atmospheric pressure (non-pressurized) and
therefore must be allowed to drain freely with gravity only. Please ensure that
there are no blockages along the condensate drain tube. All portions of the
condensate drain (neutralizer and drain tube) must be at a lower eleva-
tion than the micro boiler to prevent condensate water from building up
inside the heat exchanger.
Condensate cannot be effectively neutralized if the neutralizer elements inside
the Neutralizer accessory have been completely consumed. if this happens,
condensate will remain acidic and can possibly cause damage to items such
as pipes, concrete, etc., if drained improperly.
The neutralizer cartridge is designed to last for 3 years before replacement.
However, the actual life of the neutralizer may vary, depending on the applica-
tion and usage. Please ensure that the cartridge is properly replaced before
the neutralizer elements have been completely consumed.
All preventive measures and safety practices must be adhered to when drain-
ing condensate. The manufacturer will not be responsible for any damage
caused by condensate.
A drain pan, or other means of protection against water damage, is required to
be installed under the micro boiler in case of leaks.
ELECTRICAL CONNECTIONS
Follow the electrical code requirements of the local authority having jurisdic-
tion. In the absence of such requirements, follow the current edition of the Na-
tional Electrical Code ANSI/NFPA 70 in the U.S. or the current edition of CSA
C22.1 Canadian Electrical Code Part 1 in Canada.
When servicing or replacing parts with the micro boiler, label all wires prior to
disconnection to facilitate an easy and error-free reconnection. Wiring errors
can cause improper and dangerous operation. Verify proper operation after
servicing.
Failure to observe these warnings could result in personal injury or loss of life.
This unit comes with a power plug instead of a junction box.
WARNING
WARNING