Manual

15
ELECTRO-WELLS
Fuel Smart HydroStat
installed with Electro-Well™
When installed with the Hydrolevel Electro-Well, Fuel
Smart HydroStat will provide
both
temperature and low
water cut-off functionality. If the control was supplied
by the boiler manufacturer, it was installed with an
Electro-Well. The Electro-Well is available separately
for field installations.
Electro-Well™ Models
1/2" CLEARANCE
1/2" CLEARANCE
1/2" CLEARANCE
IIMMPPOORRTTAANNTT::
Fo
r proper opera-
tion of the low
water cut-off func-
tion, there must
be a minimum of
½" clearance
between the cop-
per well tube and
any surface within
the boiler.
HydroStat 3200-Plus Instructions: HydroStat Instructions.8pg 11/14/13 3:34 PM Page 15