OPTIONAL FEATURES continued
Circulator Activation Options
When in the default mode, the HydroStat activates the circulator (C1/C2 contacts) on calls to T/TV. The control can be pro-
grammed to activate the circulator on calls to I1/I2 in place of, or in addition to, calls to T/TV.
To change how the Circulator is activated
1. Turn the LO TEMP dial to access the Program Mode indicated in the display as
2. Turn the HI TEMP dial to select feature
3. Push the Test/Settings Button to select between the following options:
- Circulator on T/TV call only
- Circulator on I1/I2 call only
- Circulator on both T/TV & I1/I2 calls
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 6)
Circulator Hold Off (Enhanced Condensing Protection)
To reduce the potential for condensing, on a call for heat the control will allow the boiler to heat to 125°F prior to energizing the
circulator. Once energized, the circulator will remain on for the duration of the heating call unless the boiler temperature drops
below 115°F. If this occurs, the circulator will re-energize when the boiler returns to 125°F.
To activate Circulator Hold Off
1. Turn the LO TEMP dial to access the Program Mode indicated in the display as
2. Turn the HI TEMP dial to select feature
3. Push the Test/Settings Button to turn Circulator Hold Off or
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 6)
Low Water Cut-Off Function
To turn off Low Water Cut-Off
1. Turn the LO TEMP dial to access the Program Mode indicated in the display as
2. Turn the HI TEMP dial to select feature
3. Push the Test/Settings Button to turn Low Water Cut-Off or
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 6)
RESTORING FACTORY DEFAULT SETTINGS ON NEXT PAGE