Overview of Primary Product

Submittal Data Information
Probe Style Low Water Cut-Off - Residential Hot Water Boilers
Auto Reset with Burner Circuit Test Button
Effectuve: July 1, 2010
Supercedes: New
SF-1100
JOB______________ENGINEER_____________CONTRACTOR_____________
Item Number Model Number Notes
Low Maintenance - No moving
parts to wear or hang up, as in
float devices
Features
Test Button - Tests control
operation without lowering the
water level.
Standard Application
Safgard 1100 Series Controls are used as the primary low water cut-off
device on residential hot water boilers.
Operation
Hydrolevel controls utilize a non-moving, heavy duty, electronic probe to
sense liquid levels. The probe can be installed in an equalizing line or
directly into a boiler or water tank in accordance with manufacturers
instructions and local and State codes. When water is in contact with the
probe, it completes a circuit between the stainless steel probe tip and the
tank or boiler surface in which the probe is installed. When water level
drops below the probe, the circuit opens. Hydrolevel low water cut-offs for
hydronic heating systems use the water signal to allow the burner to operate.
If the water level drops below the probe, the circuit opens and the cut-off
shuts down the burner.
Automatic Reset - Shuts down
the burner when water drops
below the probe. Automatically
restores the burner circuit upon
return of a safe water level.
More Probe Plate Space -Large
probe tip puts more conductive
surface in the water, leading to
more dependable operation and
less chance of nuisance boiler
shutdowns.
Compact Size - Designed to fit
in tight spaces.
Power and Low Water LED
Indicators -
Makes troubleshooting
fast and easy.
Model 1150
Model Voltage Auto Reset Test Button ICC Compliant
1100 24VAC
1150 120VAC
MATERIALS OF CONSTRUCTION
Control Housing
Probe Insulator
Probe Tip
High Temp. PPE
High Temp. PPE
316 Stainless Steel
83 Water Street, New Haven, CT 06511
(800) 654-0768
www.hydrolevel.com
Model 1100
Dimensions
Specifications
Switch Contacts......................SPST
Input Voltage................24VAC/60HZ
(Model 1100)
Input Voltage..............120VAC/60HZ
(Model 1150)
Switching Capacity...............5.8 FLA
(Model 1150)
Switching Capacity..................50 VA
(Model 1100)
Power Consumption..................1 VA
(Model 1100)
Power Consumption............ ...2.6 VA
(Model 1150)
Agency Listing.....................U.L. 353
NEMA Classification.............NEMA 1

Summary of content (1 pages)