Install Instructions

1
83 Water Street New Haven, CT 06511 Phone (203) 776-0473 FAX (203) 773-1019 www.hydrolevel.com
MODEL 3150
Combination Low Water
Cut-Off & Universal
Temperature Limit Control
120 VAC Operating Voltage
PATENT PENDING
WARNING
Electrical shock hazard. To prevent electrical shock, death or
e
quipment damage, disconnect power supply before
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
CAUTION
To prevent serious
b
urns, boiler
should be thoroughly cooled before installing or
servicing control.
Dual Function Design HydroStat performs both high temperature limit and low
water cut-off functions when installed with a Hydrolevel Electro-Well™.
Replaces Common Aquastat
*
M
odels Can be installed on existing immersion
wells to replace both cold-start and triple-action Aquastats
®
. Industry standard
wiring designations make change-outs quick and easy.
Digital Display Easy to read LED continually displays boiler temperature. Also
d
isplays temperature limit and differential settings during adjustment.
Easy to Set Dials for setting temperature limits and differentials eliminate
complicated programming.
Advanced Micro-Controller Design Utilizes dual thermistor technology for
better accuracy, response and reliability.
*Aquastat is a registered trademark of Honeywell International, Inc.
HydroStat installed
with Electro-Well™
When installed with the Hydrolevel Electro-Well,
HydroStat will provide
both
temperature and low water
cut-off functionality. If the control was supplied by the
boiler manufacturer, it was installed with an Electro-
Well. The Electro-Well is available separately for field
installations. See Electro-Well models on page 8.
OR
IMPORTANT When installed on a standard immersion well, HydroStat will not provide low water cut-off functionality.
HydroStat installed with
a standard immersion well
For field replacement of common Aquastat
®
models,
HydroStat can be installed with the immersion well
already on the boiler. In this configuration, HydroStat
will provide the temperature functionality of the control
being replaced, but will not provide low water cut-off
functionality. The “LWCO Active” LED will not illuminate.