SPECIFICATIONS HYDROSTAT MODEL 3150
DIMENSIONS
LOW WATER CUT-OFF TEST PROCEDURE
ELECTRO-WELLS
LIMITED MANUFACTURERʼS WARRANTY
We warrant products manufactured by Hydrolevel Company to be free from defects in
material and workmanship for a period of two years from the date of manufacture or
one year from the date of installation, whichever occurs first. In the event of any claim
under this warranty or otherwise with respect to our products which is made within
such period, we will, at our option, repair or replace such products or refund the pur-
chase price paid to us by you for such products. In no event shall Hydrolevel Company
be liable for any other loss or damage, whether direct, indirect, incidental or conse-
quential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other
warranty or guarantee, express or implied, including, without limitation, any warranty
of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be
assigned or transferred and any unauthorized transfer or assignment thereof shall be
void and of no force or effect.
Input voltage 120 VAC, 60 HZ
Burner contacts 7.4 FLA, 44.4 LRA@120 VAC
Circulator contacts 5.8 FLA, 34.8 LRA@120 VAC
HydroStatʼs low water cut-off function is active when the control is installed on a Hydrolevel Electro-Well. To test the low water cut-off function:
Turn off power to the control.
Set the thermostat to call for heat.
Gently slide the sensor out of the well to simulate a low water condition.
Re-energize power to the control. The red LOW WATER light should come on and the burner should not fire.
Turn power off again and rein-
stall the sensor in the well.
Re-energize power to the control. The green LWCO ACTIVE light should illuminate and the burner should
fire.
MAINTENANCE
Remove the Electro-Well from the heating system every five years and clean any scale or sediment deposits from all parts that are exposed to
the boiler water. After cleaning, reinstall the well using pipe sealing compound. Teflon tape is not recommended.
Operating range low limit Off or 110°F - 200°F
Operating range high limit 100°F - 220°F
Operating range differential 10°F - 30°F