Submittal Sheet

Submittal Data Information
Combination Temperature Limit, Low Water Cut-Off and Boiler Reset
Residential Hot Water Boilers
Effective: September 1, 2010
Supercedes: New
HYD-3200
JOB______________ENGINEER_____________CONTRACTOR_____________
Dial Type Settings-Allows for quick
and easy set-up.
Features
Indirect Water Heater Compatible-
Bypasses Thermal Targeting
function on calls from the indirect
water heater, allowing the boiler to
fire to the high limit setting, ensuring
quick response to hot water needs.
Dynamic Display-Continually
displays boiler temperature.
Changes to indicate control settings
when Test/Settings button is
pressed. Displays Pur when control
is in Thermal Pre-Purge mode.
Test/Settings Button-Tests the low
water cut-off operation when installed
with a Hydrolevel Electro-Well.
Displays all settings when
sequencially depressed.
83 Water Street, New Haven, CT 06511
(800) 654-0768
www.hydrolevel.com
Diagnostic Lights-Continually
indicate which features are active
and if the control is holding off the
burner for any reason. No
complicated menus to scroll through.
Circulator Hold-Off-Delays
circulator on a call for heat until the
boiler temperature reaches 120 F
to reduce potential for condensing.
Item Number Model Number Notes
Specifications
Input Voltage:..............120VAC/60HZ
Power Consumption................2.6 VA
Agency Listing.....................U.L. 353
NEMA Classification.............NEMA 1
Circulator Contacts:5.8 FLA, 34.8 LRA
@120VAC
Burner Contacts (3250): 7.4 FLA, 44.4 LRA
@120VAC
Burner Contacts (3200): 30VA@ 24VAC
Operating Range
Low Limit:..........Off or 110 F to 200 F
Operating Range
High Limit:..................100 F to 220 F
Standard Application
Hydrolevels Fuel Smart HydroStats are installed primarily on residential oil or
gas fired water boilers. Fuel Smart HydroStat combines the functions of
temperature limit control, low water cut-off and energy saving boiler reset into
a single control.
Operation
How Thermal Pre-Purge Works
To further enhance fuel efficiency, Fuel Smart HydroStat is also equipped with
a Thermal Pre-Purge feature. When activated, the control will purge standing
heat in the boiler at the start of any thermostat call, supplying the free latent
energy to the heating zone that is calling. If this latent heat is not sufficient to
satisfy the thermostat, the control will then energize the burner. This feature
works with single and multi-zone heating systems utilizing circulators or zone
valves and requires no change in wiring.
Thermal Targeting Technology analyzes thermostat activity and continually
evaluates how much heat the house requires. When it is very cold outside, the
heat demand is high and the Fuel Smart HydroStat will raise the boilers Target
temperature to provide needed heat to the home. When the outside temperature
is milder, the heat demand is lower. During these periods, the Fuel Smart
HydroStat will lower the boilers Target temperature - saving fuel - while
continuing to provide comfort to the house.
How Thermal Targeting Works
When installed with Hydrolevels ElectroWell, Fuel Smart HydroStat will provide
automatic reset Low Water Cut-Off functionality to any boiler installation. When
the Fuel Smart HydroStat is installed on an electrowell a green LWCO active
light will automatically illuminate on the control.
Low Water Cut-Off Function
Dimensions