Manual

Page 1
2510 AIO Supplemental Insert
Overview:
The AIO valve is designed for use when water containing contaminates subjected to oxidation is encountered.
The water passes through the AIO valve then passes through the tank containing oxygen enriched lter media.
The oxygen reduces all contaminates in the water to an oxide, or in the case of hydrogen sulde gas, it is reduced
to a molecule of acid.
Regeneration as follows:
Backwash (BW): The backwash cycle washes oxidized contaminates to drain and
Cycle Step #1 reclassies the media bed.
Air Draw (BD): Air Draw empties water from tank and replenishes oxygen to lter
Cycle Step #2 media.
Rapid Rinse (RR): Rapid Rinse purges excess atmosphere from the media tank and
Cycle Step #3 distributor.
NOTE: Due to the oxygen in the media tank, maximum 80 PSI for operation.
SXT Programming:
Programming
Abbreviation
Programming
Denition
* Option
Abbreviation
Option Denition
DF Display Format GAL Gallons – 12 hour time
VT Valve Type DF 1b Downow Single Backwash
CT Control Type tc Time Clock – Regenerates based on days
NT Number of Tanks 1 Single Tank
DO Day Override 3 Days Between Regeneration – In
conditions of high water usage and/or
high levels of contaminants, the AIO may
need to regenerate more frequently than
once every three days. DO NOT set the
regeneration day override for a longer
period than three days, as the lter media
can become fouled with contaminates,
rendering the AIO ineffective.
RT Regeneration
Time
12:30 AM Regeneration Time – If there is a need to
change the factory default, then make
sure the time of regeneration is not the
same with any other water treatment
equipment in the system.
BW Backwash 14 See AIO Overview Above
BD Air Draw 40 See AIO Overview Above
RR Rapid Rinse 4 See AIO Overview Above
BF Brine Fill Off Not Applicable
* Factory Defaults
Reference SXT service manual for programming information.