APPLICATION CONTINUED
ANTIFREEZE CORRECTION FACTORS DATA
ANTIFREEZE
ETHYLENE GLYCOL
10%
20%
30%
40%
50%
COOLING CAPACITY
0.995
0.992
0.987
0.983
0.979
HEATING CAPACITY
0.991
0.982
0.977
0.969
0.961
PRESSURE DROP
1.070
1.130
1.180
1.260
1.280
Table 8 - Antifreeze Correction Factors Ethylene Gycol
ANTIFREEZE
PROPYLENE GLYCOL
10%
20%
30%
40%
50%
COOLING CAPACITY
0.990
0.980
0.970
0.960
0.950
HEATING CAPACITY
0.987
0.975
0.962
0.942
0.930
PRESSURE DROP
1.070
1.150
1.250
1.370
1.420
Table 9 - Antifreeze Correction Factors Propylene Gycol
ANTIFREEZE
METHANOL
ANTIFREEZE
ETHANOL
10%
20%
10%
20%
COOLING CAPACITY
0.980
0.972
COOLING CAPACITY
0.991
0.951
HEATING CAPACITY
0.950
0.970
HEATING CAPACITY
0.995
0.960
PRESSURE DROP
1.023
1.067
PRESSURE DROP
1.035
0.960
Table 8 - Antifreeze Correction Factors Methanol
Table 9 - Antifreeze Correction Factors Ethanol