34 WSV6 Vertical Series – IOM
CONTROLS CONTINUED
ELECTRONIC TEMPERATURE CONTROLLER
(ECONOMIZER)
The electronic temperature controller must be configured
prior to the initial unit start-up in order for the economizer
parameters be entered.
FIGURE 17 – Electronic Temperature Controller
VIEWING AND CHANGING BASIC MENU
VALUES
To access the Basic menu and view and change the Basic
parameter values, complete the following steps.
1. On the Main screen, press
MENU. The LCD displays OFF,
which is the first parameter code screen displayed in the
Basic menu.
2. To scroll through all of the basic parameter codes and
display the preferred code, press
Down or Up.
3. With the preferred parameter code displayed, press
MENU to display the current parameter value for the code.
4. With the current parameter value displayed, press
Down
or
Up to scroll through all of the parameter’s usable values
and display the preferred value.
5. With the preferred parameter value displayed, press
MENU to save the displayed value and go to the next
parameter code.
6. To exit the Basic menu and go to the Advanced menu,
simultaneously press and hold Down or Up for 5 seconds.
ECONOMIZER PARAMETER CODES AND
MODES OF OPERATION
RELAY OFF TEMPERATURE (OFF)
Select the temperature in which the 3-way valve de-
energizes and the unit returns to cooling mode. Once the
controller reaches the relay off temperature, the green LED
on the controller will turn off. It is recommended that this
temperature be set between 50-55°F.
RELAY ON TEMPERATURE (ON)
Select the temperature in which the 3-way valve energizes
and the unit enters into economizer mode. Once the
controller reaches the relay on temperature, the green LED
on the controller will turn on. It is recommended that this
temperature be set between 40-45°F.
ANTI-SHORT CYCLE DELAY (ASD)
Select the minimum time that the output relay remains off
(de-energized) before the next on-cycle can begin. Setting
an ASD interval overrides the output relay and prevents the
3-way valve from being energized during this time. When
the ASD value is greater than 0, the delay interval will begin
every time the controller turns on and every time that an
off-cycle begins. It is recommended that this be set to 3.
SENSOR FAILURE MODE (SF)
Describes the functionality of the control in the event of a
sensor failure. Value must be set to 0.
RECOMMENDED CONTROLLER PARAMETERS
PARAMETER
CODE
PARAMETER
DESCRIPTION
RECOMMENDED
PARAMETERS
Un
Relay Off Temperature
55
Off
Relay On Temperature
45
On
Anti-Short Cycle Delay
3
SO
Sensor Failure Mode
0
Table 13 – WSCM DIP Switch Functions