CONTROLS CONTINUED
WSCM SAFETY FEATURES
WSCM DIP SWITCH FUNCTIONS
FUNCTION
OFF
ON
DIP SWITCH 1
1.1
Compressor Delay
No Delay
5s Delay
1.2
Motor Type
PSC Motor
ECM Motor
1.3
Blower Time Delay
None
45s
1.4
Dehumidification
None
Dehum
1.5
Boilerless
Off
On
1.6
Boilerless Setpoint
40°F
50°F
1.7
Vacated Premises
1hr
2hr
DIP SWITCH 2
2.1
Accessory Relay Control
With Fan
With Comp
2.2
Compressor Delay
None
60s
2.3
Accessory Relay 2 Control
With Fan
With Comp
2.4
Fan Delay
None
30s
Table 16 WSCM DIP Switch Functions
CONTROL BOX DETAIL
FIGURE 18 Control Box Layout
ASSEMBLY
Once box is removed completely, line up the control panel
back in place of the unit and tighten screws on the base
plate and on the front panel. Plug back any harnesses
previously removed.
REMOVAL
1) Ensure that all electrical power is removed from the
unit and that the local disconnect is locked out.
2) Remove the screws on the front electrical panel with
a ¼” hex head driver.
3) Remove the electrical front panel and access the
electrical box
4) Disconnect electrical harnesses
5) Remove the two ¼” hex header screws holding the
electrical box in place on the bottom and side.
Remove electrical box from unit.


Disconnect all power supplies before servicing. Lock
out/tag out to prevent accidental electrical shock.

There may be multiple power sources supplying the
unit.