Phau Ntawv Qhia
WSV6 VERTICAL SERIES - IOM
WSV6 Vertical Series – IOM 45
PERFORMANCE DATA CONTINUED
PRESSURE & TEMPERATURE DATA
WSV6048 PRESSURE & TEMPERATURE DATA
Entering
Water
Temp
Water Flow
Rate
COOLING
HEATING
Suction
Pressure
Discharge
Pressure
Air Temp
Drop
Water
Temp Rise
Suction
Pressure
Discharge
Pressure
Air Temp
Drop
Water
Temp Rise
°F
GPM
psig
psig
°F
°F
psig
psig
°F
°F
20
6
Operation Not Recommended
Operation Not Recommended
9
12
30
6
65-75
271-281
19-25
7-11
9
69-79
275-285
20-26
4-8
12
73-83
280-290
21-27
3-7
50
6
122-132
222-232
24-30
20-24
104-114
310-320
25-31
9-13
9
120-130
201-211
25-31
13-17
111-121
316-326
26-32
5-9
12
120-130
191-201
25-31
9-13
115-125
320-330
27-33
4-8
70
6
127-137
293-303
23-29
20-24
144-154
348-358
32-38
12-16
9
125-135
269-279
23-29
13-17
155-165
359-369
34-40
8-12
12
124-134
257-267
24-30
9-13
161-171
365-375
35-41
5-9
90
6
132-142
380-390
22-28
19-23
193-203
395-405
40-46
15-19
9
130-140
354-364
22-28
12-16
209-219
411-421
42-48
10-14
12
129-139
341-351
22-28
9-13
217-227
420-430
43-50
7-11
110
6
138-148
485-495
21-27
18-22
Operation Not Recommended
9
136-146
457-467
21-27
12-16
12
135-145
444-454
21-27
8-12
Table 24 – WSV6048 Pressure & Temperature Data