Phau Ntawv Qhia
WSV6 VERTICAL SERIES - IOM
WSV6 Vertical Series – IOM 47
PERFORMANCE DATA CONTINUED
PRESSURE & TEMPERATURE DATA
WSV6072 PRESSURE & TEMPERATURE DATA
Entering
Water
Temp
Water Flow
Rate
COOLING
HEATING
Suction
Pressure
Discharge
Pressure
Air Temp
Drop
Water
Temp Rise
Suction
Pressure
Discharge
Pressure
Air Temp
Drop
Water
Temp Rise
°F
GPM
psig
psig
°F
°F
psig
psig
°F
°F
20
9
Operation Not Recommended
Operation Not Recommended
13.5
18
30
9
56-66
275-285
20-26
5-9
13.5
59-69
281-291
22-28
3-7
18
64-74
283-293
23-29
2-6
50
9
122-132
219-229
25-31
18-22
85-95
309-319
28-34
8-12
13.5
121-131
202-212
26-32
12-16
91-101
316-326
29-35
5-9
18
120-130
193-203
26-32
8-12
95-105
320-330
30-36
3-7
70
9
126-136
288-298
24-30
18-22
119-129
351-361
36-42
11-15
13.5
125-135
268-278
24-30
11-15
129-139
363-373
38-44
7-11
18
125-135
259-269
25-31
8-12
135-145
370-380
40-46
5-9
90
9
132-142
373-383
23-29
17-21
160-170
403-413
46-52
14-18
13.5
130-140
351-361
23-29
11-15
175-185
422-432
49-55
10-14
18
130-140
341-351
23-29
8-12
184-194
433-443
51-57
7-11
110
9
137-147
474-484
21-27
17-21
Operation Not Recommended
13.5
136-146
451-461
22-28
11-15
18
135-145
441-451
22-28
8-12
Table 26 – WSV6072 Pressure & Temperature Data