Phau Ntawv Qhia
WSV6 VERTICAL SERIES - IOM
48 WSV6 Vertical Series – IOM
PERFORMANCE DATA CONTINUED
WATER PRESSURE DROP DATA
WATER FLOW PRESSURE DROP DATA
WSV6009
Flow Rate
(GPM)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
Pressure Drop
0.2
0.9
1.9
3.0
4.5
6.3
8.2
WSV6012
Flow Rate
(GPM)
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Pressure Drop
1.0
2.0
3.3
4.8
6.6
8.7
10.9
WSV6018
Flow Rate
(GPM)
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Pressure Drop
1.0
2.0
3.3
4.8
6.6
8.7
10.9
WSV6024
Flow Rate
(GPM)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
Pressure Drop
1.4
2.0
2.6
3.3
4.1
5.0
6.0
WSV6030
Flow Rate
(GPM)
6.0
7.0
8.0
9.0
10.0
11.0
12.0
Pressure Drop
2.3
3.0
3.9
4.8
5.8
6.9
8.0
WSV6036
Flow Rate
(GPM)
6.0
8.0
10.0
12.0
14.0
16.0
18.0
Pressure Drop
1.1
1.9
2.8
4.0
5.2
6.7
8.2
WSV6042
Flow Rate
(GPM)
7.0
9.0
11.0
13.0
15.0
17.0
19.0
Pressure Drop
1.4
2.1
3.0
4.1
5.2
6.6
8.0
WSV6048
Flow Rate
(GPM)
12.0
14.0
16.0
18.0
20.0
Pressure Drop
2.6
3.5
4.7
5.9
7.4
WSV6048
ECONOMIZER
Flow Rate
(GPM)
12.0
14.0
16.0
18.0
20.0
Pressure Drop
6.5
8.8
11.8
14.8
18.5
WSV6060
Flow Rate
(GPM)
12.0
14.0
16.0
18.0
20.0
22.0
24.0
Pressure Drop
2.6
3.3
4.2
5.1
6.2
7.3
8.5
WSV6060
ECONOMIZER
Flow Rate
(GPM)
12.0
14.0
16.0
18.0
20.0
22.0
24.0
Pressure Drop
6.0
8.2
10.6
13.4
16.5
19.9
23.7
WSV6072
Flow Rate
(GPM)
12.0
14.0
16.0
18.0
20.0
22.0
24.0
Pressure Drop
2.6
3.3
4.2
5.1
6.2
7.3
8.5
WSV6072
ECONOMIZER
Flow Rate
(GPM)
12.0
14.0
16.0
18.0
20.0
22.0
24.0
Pressure Drop
6.0
8.2
10.6
13.4
16.5
19.9
23.7
Table 27 – Pressure Drop Data