Phau Ntawv Qhia

WSV6 VERTICAL SERIES - IOM
WSV6 Vertical Series IOM 7
GENERAL INFORMATION

DO NOT use these units as a source of heating or cooling
during the construction process. Mechanical components
and filters can become clogged with dirt and debris, which
can cause damage to the system.
The manufacturer does not warrant equipment subjected
to abuse.


Before servicing equipment, ALWAYS turn off all power to
the unit. There may be more than one disconnect switch.
Electrical shock can cause injury or death.
Clear surrounding area of all tools, equipment, and debris
before operating this unit.
These instructions are provided for the installation of the
WSV6 water source heat pump specifically. For any other
related equipment, refer to the appropriate manufacturer’s
instructions.

This water source heat pump must never be operated
under any circumstances without an air filter in place.

Material in this shipment has been inspected at the
factory and released to the transportation agency in
good condition. When received, a visual inspection of all
cartons should be made immediately. Any evidence of
rough handling or apparent damage should be noted on
the delivery receipt in the presence of the carrier’s
representative. If damage is found, a claim should be
immediately filed against the carrier.
The WSV6 water source heat pump is designed for indoor
installation only. Installation of this equipment, wiring,
ducts, and any related components must conform to
current agency codes, state laws, and local codes. Such
regulations take precedence over general instructions
contained in this manual.

Extreme caution must be taken that no internal damage
will result from screws that are drilled into the cabinet.
INTRODUCTION
The HydroTech WSV6 series water to air heat pump
provide the best combination of performance, efficiency
and reliability in a compact form factor. The WSV6 series
comes standard with ECM blower motors for high
efficiency and comfort. All WSV6 models feature double
compressor vibration isolation for quiet operation, easy
to remove blower housing for quick service, as well as a
single compressor designs to lower system complexity
and improve serviceability.
All WSV6 models are certified to AHRI ISO Standard
13256-1. The WSV6 models are designed to operate
with fluid temperatures between 50°F to 110°F in
cooling mode and 50°F to 90°F in heating mode for
continuous operation. For operation below 50°F or
above 90°F entering water temperature, extended range
(insulated tubing) option is needed, and sufficient water
flow is required to prevent freezing. Antifreeze solution
is required for any application with entering water below
50 degree F.
Cooling Tower/Boiler and Geo Thermal applications
should have sufficient antifreeze solution when required
to protect against extreme conditions and equipment
failure. Frozen water coils are not covered under
warranty.
These installation instructions are intended as a general
guide only, for use by an experienced, qualified contractor.

Do not use this water source heat pump during any phase
of construction.