7. Operation <Practical Steps>
7.8 Zone Signal Output
Two types of zone output signals are available: zone output (ZONE1) and position zone output (PZONE). The
boundaries defining the signal ON range are set differently for each zone output.
[1] Zone output (ZONE1) --- Set by parameter No. 1/No. 2.
[2] Position zone output (PZONE) --- Set in the “Zone boundary-“ and “Zone boundary+” fields of the position
table.
Whether these signals are available or not varies depending on the PIO pattern, as shown below.
{: Available / x: Not available
PIO pattern
Signal classification
0 1 2 3 4 5
Zone output (ZONE1)
{
x x x
{{
Position zone output (PZONE)
{{{
x
{{
Example of use in operation) Move the actuator from the home to the 150-mm position (position 1) and output a
zone signal once the actuator enters the range between 40 mm and 120 mm.
Method) x Zone output (ZONE1)
The signal ON range is set by the “Zone boundary+” and “Zone boundary-”
parameters.
Parameter No. 1 Zone boundary+ 120 (mm)
Parameter No. 2 Zone boundary– 40 (mm)
x Position zone output (PZONE)
The signal ON range is set in the “Zone boundary+” and “Zone boundary-”
fields of the position table.
No.
Position
[mm]
Zone boundary+
[mm]
Zone boundary-
[mm]
0***
1 150.00 120.00 40.00