4. Wiring
(2) Wiring the emergency-stop switch
In many cases multiple controllers are used in a single system.
To provide an emergency-stop function for the entire system, the controller circuit is designed in such a
way that a single EMG switch is able to actuate an emergency stop in all connected controllers.
[Example of recommended circuit]
(Note 1) To cut off the motor drive power supply in conformance with safety category 2, connect 24V to
the EMG terminal and a contactor or other contact device to the MPI/MPO terminals.
(Note 2) The current consumption of the internal relay is 10 mA or less.
Motor
power
supply
External EMG
reset switch
External EMG circuit
EMG switch on
teaching pendant
Relay
ACON-C controller
Coil current:
0.1 A or less
Connection detection circuit
Controller
power
supply