5. Operation of CON Related Controllers
38
Zone output signal
Zone output signal
Zone output signal
Home
Backward
end
Forward
end
Midway
point
(7) Incremental
Specify absolute coordinates or incremental coordinates.
The factory setting is 0.
0: Absolute coordinate specification
1: Incremental coordinate specification
Warning: Be sure to specify absolute coordinates on PCON-C/CG/CF, PCON-CA, ACON-C/CG,
SCON-C, SCON-CA, ROBONET, ERC3 PIO Converter and MSCON (Remote I/O
mode) controllers of solenoid valve mode 2, or PCON-CY and ACON-CY controllers of
solenoid valve mode 1.
If incremental coordinates are specified on these controllers, a position data error
occurs.
(8) Zone +/-
Define, for the standard type, the zone in which the zone output signal turns ON.
For added flexibility, these parameters can be set differently for each target position.
[Setting example]
No. Position [mm] Zone + [mm] Zone - [mm] Remarks
0 5.00 100.00 0.00 Backward end
1 380.00 400.00 300.00 Forward end
2 200.00 250.00 150.00
Intermediate
position
Movement command to backward end
Movement command to forward end
Movement command to intermediate position
(9) Threshold
With PCON-C/CG/CF, PCON-CA controllers, a load output signal (PIO) is output if the command torque
exceeds the value (%) set in "Threshold" inside the verification range.
The verification range is set by "Zone+/Zone-."
It is used to determine if press-fitting action was performed successfully.
* For details, refer to the operation manual for your PCON-C/CG/CF, PCON-CA controller.