Manual

22
2. X-SEL-J/K/P/Q/JX/KX/PX/QX
I/O parameters for X-SEL J/K types
No. Parameter name
Default value
(reference)
Input
range
Setting Remarks
1 I/O port assignment type 0 0 ~ 20 0 0: Fixed assignment
1: Automatic assignment (Priority:
Assigned from slot 1)
* Ports are assigned consecutively only
for slots where a board is physically
installed, starting from slot 1, for safety
reasons.
2 Input port start number for standard I/O
based on fixed assignment (I/O1)
000 -1 ~ 599 000 0 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
3 Output port start number for standard
I/O based on fixed assignment (I/O1)
300 -1 ~ 599 300 300 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
4 Input port start number for expansion
I/O1 based on fixed assignment (I/O2)
-1 -1 ~ 599 -1 0 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
(Slot immediately next to the standard I/O
slot)
5 Output port start number for expansion
I/O1 based on fixed assignment (I/O2)
-1 -1 ~ 599 -1 300 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
6 Input port start number for expansion
I/O2 based on fixed assignment (I/O3)
-1 -1 ~ 599 -1 0 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
7 Output port start number for expansion
I/O2 based on fixed assignment (I/O3)
-1 -1 ~ 599 -1 300 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
8 Input port start number for expansion
I/O3 based on fixed assignment (I/O4)
-1 -1 ~ 599 -1 0 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
9 Output port start number for expansion
I/O3 based on fixed assignment (I/O4)
-1 -1 ~ 599 -1 300 + (multiple of 8) (Invalid, if a value is
entered with a negative sign.)
10 Error monitor for standard I/O (I/O1) 2 0 ~ 5 2
11 Error monitor for expansion I/O1 (I/O2) 0 0 ~ 5 0
12 Error monitor for standard I/O2 (I/O3) 0 0 ~ 5 0
13 Error monitor for expansion I/O3 (I/O4) 0 0 ~ 5 0
0: Do not monitor
1: Monitor
2: Monitor (Do not monitor 24-V I/O power
supply errors)
(Main application version 0.55
or later)
3: Monitor (Monitor 24-V I/O power supply
errors only)
(Main application version 0.55
or later)
14 Number of ports used for remote input
via network I/F card
64 0 ~ 256 32 Multiple of 8
15 Number of ports used for remote output
via network I/F card
64 0 ~ 256 16 Multiple of 8
I/O1 through I/O4 indicate slot numbers.