Instruction Manual

Chapter 4 Operation 4.2 Operation in Positioner Mode
4.2.3 Operation in Positioner Mode 2 (Operation Using PIO Converter)
201
EMG
Servo
T
26ms
Lock
Release
PEND
Brake Excitation
T (before detecting excitation) = SON signal identification (6ms) + Excitation detection time (T1
+ T2) × Number of retry (10 times Max.) + Servo ON delay
time (T3)
T (after detecting excitation) = SON signal identification (6ms) + Servo ON delay time (T3)
T1 : Parameter No.30 It differs depending on the setting of excitation detection type.
Set Value = 0 ĺ 160ms
Set Value = 1, 2 ĺ 220ms
T2 : Parameter No.29 Setting of excitation phase signal detection time
It is set to 10ms in the initial setting.
T3 : Fixed to 20ms
(Note) Excitation check operation is performed at the first servo-on process after the power is
turned ON, or when the home return is completed for the simple absolute type to
identify the magnetic poles of the motor.
PEND would not turn ON in the pause condition.